| 
Code Book
Code of the Township of Abington
[ Back
to Table of Contents ]
 |
|
Search This Page
Type in the text you wish to locate on this
page (press the "Find" button
again or "Alt +S" to continue
the search and find the next instance of
the word you are looking for):
|
|
 |
PART II GENERAL LEGISLATION: Chapter 62, BUILDING
CONSTRUCTION
[HISTORY: Adopted by the Board of Commissioners of
the Township of Abington as indicated in article histories.
Amendments noted where applicable.]
GENERAL REFERENCES
Fire prevention -- See Ch. 85.
Housing standards -- See Ch. 98.
Numbering of buildings -- See Ch. 111.
Plumbing -- See Ch. 121.
Sewers and sewage -- See Ch. 132.
Subdivision and land development -- See Ch. 146.
Swimming pools -- See Ch. 149.
Zoning -- See Ch. 162.
ARTICLE I, General Standards [Adopted 5-10-1979 by
Ord. No. 1485;EN amended in its entirety 7-10-1997 by
Ord. No. 1795]
62-1. Adoption of standards by reference.
The Township of Abington, in order to regulate construction,
alteration, repair, removal, demolition, use, location,
occupancy and maintenance of buildings and structures
within the township, hereby adopts the provisions of
the BOCA Basic Building Code 1996, Thirteenth Edition,
as published by the Building Officials and Code Administrators
International, Inc., and the whole thereof, save and
except such portions as are hereinafter deleted, modified
or amended, of which not less than one copy has been
and now is filed in the office of the Secretary of the
Township of Abington, 1176 Old York Road, Abington,
Pennsylvania, and the same is hereby adopted and incorporated
as fully as if set out at length herein, and from the
date on which this chapter shall take effect, the provisions
thereof shall be controlling within the limits of the
Township of Abington.
62-2. Amendments.
Changes and additions to the BOCA Basic/National Building
Code, 1996, Thirteenth Edition, are as follows:
A. In section 101.0, insert "Township of Abington."
B. Section 104.1, shall provide as follows:
104.1 Code Official: The Department of Code Enforcement
of the Township of Abington shall be the Department
of Code Enforcement, and the executive official in charge
thereof, or a designated representative, shall be the
Code Enforcement Official.
C. Section 110.4, shall provide as follows:
110.4 Certificate of rodent extermination: A permit
to demolish or remove a structure shall not be issued
until the applicant shall furnish to the Code Official
a certificate from a reputable rodent exterminator which
shall state that the building or structure to be demolished
has been inspected and found to be free of rodents or
that the building or structure to be demolished has
been properly treated for the eradication of all rodents
in and about the premises.
D. Sections 107.6.1 through 107.6.3 shall provide as
follows:
107.6.1. Plot diagram: When required, there shall also
be filed, along with the application to obtain a building
permit, a suitable plot plan drawn on white paper with
black ink, to a scale of 20 feet to the inch or a larger
scale if so specified by the Building Inspector.
107.6.2. Copies of Plot Plan: Four copies of the plot
plan, drawn by a registered engineer or land surveyor,
are required for all new buildings, properly sealed.
One copy of the plot plan is usually sufficient for
additions, although extra copies may be requested by
the Building Official.
107.6.3. Plot plan information: Plot plans must show
the following information:
(1) The location of the property in relation to the
nearest intersecting street and the distance in feet
and decimal parts thereof of property therefrom, together
with a North point.
(2) The present owner of the property as of plan of
record or suitable evidence of recent purchase.
(3) How the property is marked, whether by surveyor
stakes or monuments, date of survey, and the lot numbers
and block number as of plan of record.
(4) The total lot area in square feet.
(5) The type of zoning and the proper building restriction
lines as per the Abington Township Zoning Ordinance.EN
(6) The total square feet area and percentage of the
lot covered by buildings or structures.
(7) The total square feet area of each floor.
(8) The square feet area of each green area (as defined
in the Zoning OrdinanceEN for commercial areas), the
total square feet of green area and percentage of lot
covered by such green area.
(9) Topographical lines showing existing and final.
elevations and flow of surface and rainwater from the
premises.
(10) The full width of the street and intersecting
street, all right-of-way, etc., properly marked with
dimension as of plan of record.
(11) All improvements installed and proposed, indicating
size and location.
(12) All paved areas with each parking space numbered.
(13) First floor elevation.
(14) Zoning District requirements listed in a column
with proposed data in a separate column.
(15) Engineered stormwater calculations.
(16) Any additional information as may be considered
necessary by the Building Inspector.
E. Insert a new Section 112.3, to be titled "Fees,"
and to read as follows: "The fee schedule to be
utilized in conjunction with this ordinance is as set
forth in Ordinance No. 1656,EN dated May 11, 1989. The
fee schedule is subject to change by future resolution
of the Board of Commissioners of the Township of Abington."
F. Section 116.4, Violation Penalties, shall provide
as follows:
116.4 Violation penalties: Any person who shall violate
a provision of this Code or who shall fail to comply
with any of the requirements thereof including applying
for a permit or certificate or who shall use, erect,
construct, alter, or repair a building in violation
of an approved plan or a permit of certificate issued
under the provisions of this Code shall be liable for
fines and penalties not exceeding $1,000 for each and
every offense and may be required to pay a reinspection
fee in the amount equal to the fee charged for a permit.
Such fines and penalties may be collected by suit or
summary proceeding brought in the name of the Township
of Abington before any District Justice or recovered
as debts of a like amount are now by law recoverable.
Proceedings for the violation of this Code and for the
collection of fines and penalties imposed thereby may
be commended by warrant or by summons, at this discretion
of the District Justice before whom the proceedings
is begun. All fines and penalties collected for the
violation of this Code shall be paid over to the Township
Treasury. Upon judgment against any person by summary
conviction, or proceedings by summons on a default of
the payment of the fine or penalty imposed and the costs,
the defendant may be sentenced and committed to the
township lockup for a period not exceeding five days.
Each day that a violation continues shall be deemed
a separate offense.
G. Section 121.1 shall provide as follows:
121.1 Board of Appeals: An appeal from the decision
of the Code Official may be taken to the Code Enforcement
Committee of the Board of Commissioners. Such appeal
shall be made in writing within 10 days after such decision
has been made. The appeal shall be verified by an affidavit
and shall be filed with the Township Secretary. The
appellant or his representative shall have the right
to appear and be heard, if such right is requested in
the written appeal. A prompt decision of such appeal
shall be made by the Code Enforcement Committee. In
making the decision, the Code Enforcement Committee
may vary or modify any provision of this Code where
there are practical difficulties in the way of executing
the strict letter of the law so that the spirit of the
law shall be observed, public safety secured, and substantial
justice done. Such variation or modification shall be
the minimum necessary in order to grant relief. Every
action of the Code Enforcement Committee on such appeals
shall be by resolution, copies of which shall be certified
by the Township Secretary and given to the Code Official
and mailed to the appellant.
H. Sections 201.0 and 202.0: Definitions shall be as
shown in the BOCA Basic Building Code/1996 Edition.
I. Section 421.2 shall provide as follows:
421.2 Definitions: Any such pool (swimming pool, pond,
hot tub, spa) which is more than 12 inches in depth.
J. Section 421.4 shall provide as follows:
421.4 Locations: Private swimming pools, spas, hot
tubs, ponds, etc., shall not encroach on any front yard
required by this Code, or the governing Zoning Code,
except by specific rules of the jurisdiction in which
it may be located. All other measurements are controlled
by the Abington Township Zoning Ordinance.EN
K. Section 421.9 shall provide as follows:
421.9 Swimming pool safety devices: Every person owning
land on which there is situated a swimming pool, fish
pond or other body of water which could contain 12 inches
or more of water in depth at any point, shall erect
and maintain thereon an adequate enclosure, surrounding
pool area sufficient to make such body of water inaccessible
to small children. Such enclosure including gates therein
must be not less than 4 feet above the underlying ground:
all gates must be self-closing, self-latching, with
latches placed 4 feet above the underlying ground or
otherwise made inaccessible from the outside to small
children.
(1) Wood pickets shall be 3/4 inch stock, 2 inches
maximum space between pickets.
(2) Iron or aluminum pickets shall be not less than
one inch square with a maximum of four inch spaces between.
Horizontal supports shall have not less than 16 inches
between.
(3) All wire fencing must be of the chain link type,
minimum eleven gauge, 11/2 inches by 11/2 inches maximum
openings. Wire fencing may be galvanized, plated or
vinyl coated. Vinyl shall be minimum of two gauge in
thickness.
(4) No natural barriers, pool covers or alternate devices
will suffice for swimming pool enclosures.
(5) Solid type fencing enclosures shall not be of a
greater height than six feet (one square foot for each
150 square feet of foundation space).
L. Section 602.0 shall provide as follows:
602.0 Construction requirements: All construction within
areas of the township designated as "Town Commercial,"
"Special Commercial," "Planned Business,"
"Apartment-Office," "Community Service,"
"Mixed Use" and "Suburban Industrial"
of the Zoning Ordinance of the Township of Abington,
Ordinance No. 1753, as the same may be amended from
time to time, shall conform to the requirements of Type
1, Protected (1A or 1B) or Type 2, Protected (1A or
1B) construction as set forth in Table 602. Type 3,
Type 4 and Type 5 construction shall be prohibited within
the aforesaid districts.
(1) Insert a new Section 602.1, which shall provide
as follows: Fire separation walls constructed of noncombustible
materials; (concrete, masonry block, steel stud and
drywall) with a fire rating of a minimum of one hour
are required as noted:
(a) Loading docks/mercantile space.
(b) Storage rooms/mercantile space or general use space.
(c) Wholesale or warehouse areas/office or mercantile
space.
(d) Service bays/office areas and waiting rooms.
(e) Other conditions as may be noted by the Code Official.
M. Section 707.1 shall provide as follows:
707.1 Party Walls: Party walls between all units of
residential use shall be of two-hour fire-resistive
construction, which shall consist of eight-inch hollow
concrete block or other approved masonry material of
a two-hour fire-resistive rating. These walls shall
be constructed in such manner that they will protrude
a minimum of at least 12 inches above the finished roof.
All roofs which slope at an angle of 30 or less shall
be considered as flat roofs. All roof and/or wall projections
must be constructed in such manner that they are not
an integral part of the roof or wall and must be separated
at each unit of residential use with a partition of
at least two-hour fire-resistive rating.
707.1.2 Party walls with pitched roofs: Party walls
between all units of residential use shall be of two-hour
fire-resistive construction, which shall consist of
eight-inch hollow concrete block or other approved masonry
material of two-hour fire-resistive rating. These walls
shall be constructed in such manner that they will protrude
a minimum of at least eight inches above the finished
roof. All roofs which slope at an angle in excess of
30 from the horizontal arc are to be considered as pitched
roofs. All roof and/or wall projections must be constructed
in such manner that they are not an integral part of
the roof or wall and must be separated at each unit
of residential use with a partition of at least two-hour
fire-resistive rating.
N. Section 709.2 shall provide as follows:
709.2 Crawl Spaces: In buildings and structures constructed
without basements, in which the first floor construction
does not bear directly on the ground, a space shall
be provided under the first floor not less than 36 inches
in depth and shall be surfaced with not less than two
inches of concrete; and such space shall be vented with
screened openings having a clear area of not less than
one square foot for each one hundred fifty square feet
of foundation space or shall be provided with other
means of ventilation approved by the Code Official.
Openings shall be located as close to corners as practicable
and shall provide cross ventilation on at least two
approximately opposite sides. The openings shall be
covered with corrosion-resistant mesh not less than
1/4 inch (six mm) nor more than 1/2 inch (13 mm) in
any direction.
O. Section 1110.5 shall provide as follows:
1110.5 Approvals granted by the adoption of this Code
does not preclude that applicants/owners must comply
with the "Americans with Disabilities Act"
requirements.
P. Section 1806.0 shall provide as follows:
1806.0 Footings:
1806.1 Unless the proper test and procedures are followed
as prescribed within this article, the Code Official
may prescribe whatever depth, width or thickness of
footing and foundation that the Code Official may deem
necessary, including but not limited to the use of reinforcing
rods, wire mesh, cassions, sonotubes, etc.
1806.2 All footings shall be a minimum of three feet
in depth unless otherwise directed or approved by the
Code Official. Widths of footings with the type of foundation
to be constructed: 20 inches in width for twelve-inch
concrete block and 16 inches for eight-inch concrete
block. Other changes may be permitted as site conditions
warrant or at the discretion of the Code Official. A
sump pump installed according to the Code Official's
discretion, may be required.
Q. Section 3311.0 shall provide as follows:
3311.0 Retaining walls:
3311.1: When the adjoining grade is not higher than
the legal level, the person causing an excavation to
be made shall erect, when necessary, a retaining wall
at his own expense and on his own land. Such wall shall
be built to a height sufficient to retain the adjoining
earth, shall be properly coped and shall be provided
with a guardrail or fence not less than four feet in
height.
3311.2: No fence, screening, wall or retaining wall
shall be erected on or encroach within five feet of
an established property line without first securing
a building permit.
No permit for a fence, screening, wall or retaining
wall shall be issued until satisfactory evidence is
presented to the Building Inspector of a boundary survey
with its corners properly marked by monuments or stakes
placed under the direction of a registered engineer
or land surveyor.
Walls built to retain or support the lateral pressure
of earth, water or other superimposed loads, shall be
designed and constructed of approved masonry, reinforced
concrete, steel sheet piling or other approved materials
within the allowable stresses of engineering practices,
and subject to the approval of the Township Engineer
and the Building Inspector and in conformance with the
Township of Abington Subdivision Ordinance.EN
A retaining wall of approved construction, designed
by a registered civil engineer or architect, shall be
required for all permanent land fills or excavations
which exceed three feet in height or depth along a property
boundary line, unless, a 1:1 natural slope of the land
can be maintained entirely within the boundaries of
the excavated or filled property.
Retaining walls of less than three feet in height,
erected entirely within the interior of a property and
not encroaching within five feet of boundary line, will
not require a permit.
3311.3 Fences:
3311.4 No fence, screening or wall except an open wire
fence or a retaining wall shall be erected on any property
and/or in any yard to a greater height than six feet
unless authorized by a special exception by the Zoning
Hearing Board after a public hearing.
3311.5 In any case where a fence or wall or screening
is erected within five feet of a property line, satisfactory
evidence must be presented to the Building Department
of a boundary survey with its corners properly marked
by monuments or stakes placed under the direction of
a registered engineer or land surveyor, unless the boundary
line in question can be easily established by the Building
Official.
3311.6 Any fence, screening or wall installed within
10 feet of a front property line may be of a type or
height which will create a vision obstruction for any
motorist and must be removed or installed as the Building
Official directs.
R. Section 1512.6 shall provide as follows:
1512.6 Existing roofs:
1512.6 The repair of existing roofs shall comply with
the provisions of Section 103.0. When a wood shingle
roof is replaced, it may be replaced with wood shingles.
When a wood shingle roof is to be replaced with other
than wood shingles, the wood shingles must be removed
and the roof must be sheathed with not less than 1/2
inch plywood nailed according to the requirements of
this code. Not more than two layers of asphalt shingles
may be applied to any roof.
S. Section 2114.0 shall provide as follows:
2114.0 Fireplaces and chimneys:
2114.1 Scope: The provision of this article shall control
the design, installation, maintenance, repair and approval
of all chimneys, vents, fireplaces, wood stoves and
connectors hereafter erected or altered in all buildings
and structures.
2114.1.1 Other standards: Unless specifically provided
herein, conformity to the applicable requirements for
chimney construction and vents contained in the mechanical
code listed in Appendix A shall be deemed to meet the
requirements of this Code.
2114.1.2 Minor repairs: Minor repairs for the purpose
of maintenance and upkeep which do not increase the
capacity of the heating apparatus or appliances or which
do not involve structural changes in the permanent chimney
and vents of a building may be made without a permit.
2114.1.3 General: The structural plans and specifications
shall describe in sufficient detail, the location, size
and construction of all chimneys, vents and ducts and
their connections to boilers, furnaces, appliances and
fireplaces. The thickness and character of all insulation
materials, clearances from walls, partitions and ceilings
and proximity of heating devices and equipment to wall
openings and exitways shall be clearly shown and described.
2114.1.4 Appliances: All appliances required to be
vented shall be connected to a vent or chimney, except
as provided in Section 1506.3 and as provided in the
standards listed in Appendix A for special venting arrangements.
2114.1.5 Performance test and acceptance criteria.
2114.1.6 Tests: The Building Official may require test
or tests of any chimney or vent to insure fire safety
and the removal of smoke and products of combustion.
2114.1.7 Acceptance criteria: The system shall be accepted
if the following conditions are fulfilled:
(1) There shall not be spillage at the draft hood when
any one or combination of appliances connected to the
system is in operation.
(2) Temperature on adjacent combustible surfaces shall
not be raised more than limits acceptable to nationally
recognized testing or inspection agencies.
(3) Condensation shall not be developed in a way that
would cause deterioration of the vent or chimney drip
from joints or bottom end of the vent or chimney.
(4) The draft reading taken at the place recommended
in the installation instructions shall be within the
range specified by the appliance manufacturer.
2114.1.8 Approved installations: Factory-built chimneys
and gas vents which have been tested and listed by a
nationally recognized testing or inspection agency shall
be accepted as complying with the requirements of Item
2 of Section 1502.2 when installed in accordance with
the clearance specified in their listing.
2114.1.9 Chimneys:
2114.1.10 Classification: Chimneys, as used in this
article, shall be classified as:
(1) Factory-built chimneys;
(2) Masonry chimneys; and
(3) Metal chimneys (smokestacks).
2114.1.12 General: All heating appliances, except those
appliances specifically exempted by the provisions of
Section 1506.3, shall be connected to chimneys as specified
in the chimney selection chart contained in the Mechanical
Code listed in Appendix A. Only one solid-fuel-burning
appliance shall be vented to any single passageway of
a masonry chimney or a factory-built chimney. If a gas
or oil appliance is presently connected to a chimney
passageway, a solid-fuel-burning appliance shall not
be connected.
2114.1.13 Extension: Factory-built chimneys, masonry
chimneys and metal chimneys (smokestacks) connected
to solid-fuel-burning fireplaces, stoves or heaters
shall extend at least three feet above the point where
it protrudes through the roof and at least two feet
above any obstruction within a ten-foot radius of the
chimney. Any factory-built chimney or approved metal
chimney that extends more than five feet above a roof
must be properly supported or guyed.
2114.1.14 Existing buildings:
2114.1.15 Raising existing chimneys: Whenever a building
is hereafter erected, enlarged or increased in height
so that a wall along an interior lot line, or within
three feet thereof, extends above the top of an existing
chimney or vent of an adjoining existing building, the
owner of the building so erected, enlarged or increased
in height shall carry up at his own expense, with the
consent of the adjoining property owner, either independently,
or in his own building, all chimneys connected to fuel
burning appliances. Vents within six feet of any portion
of the wall of such adjoining building shall be extended
two feet above the roof or parapet of the adjoining
building.
2114.1.16 Size of extended chimneys: The construction
of an extended chimney shall conform to the requirements
of this article for new chimneys, but the internal area
of such extension shall not be less than that the existing
chimney.
2114.1.17 Notice to adjoining owner: It shall be the
duty of the owner of the building which is erected,
enlarged or increased in height to notify, in writing,
and to secure the consent of the owner of existing chimneys
affected at least 10 days before the star.
2114.1.18 Existing chimneys: An existing chimney, except
one which does not endanger the fire safety of a building
or structure and is acceptable to the Building Official,
shall not be continued in use unless it conforms to
all requirements of this article for new chimneys.
2114.1.19 Cleanouts and maintenance: Whenever a new
chimney is completed or an existing chimney is altered,
it shall be cleaned and left smooth on the inside. If
the chimney is constructed of masonry or tile,the interior
mortar joints must be left smooth and flush. Cleanouts
or other approved devices shall be provided at the base
of all chimneys to enable the passageways to be maintained
and cleaned.
2114.1.20 Vent Systems:
2114.1.21 Listed appliances: For the purpose of determining
vent requirements, gas-fired and oil-fired appliances
shall be classified as "listed" or "unlisted."
A listed appliance is one that is shown in a list published
by an accredited authoritative testing agency qualified
and equipped for experimental testing of such appliances,
and maintaining an adequate periodic inspection of current
production of listed models and whose listing states
either that the appliance or accessory complies with
nationally recognized safety requirements or has been
tested and found safe for use in a specific manner.
Compliance may be determined by the presence of the
appliances or accessory of a label of the testing agency
stating that the appliance or accessory complies with
nationally recognized safety requirements. An unlisted
appliance or accessory is one that is not shown on such
a list or does not bear such a label. In cases where
an applicable standard has not been developed for a
given class of appliance or accessory, approval of the
authority having jurisdiction should be obtained before
the appliance or accessory is installed.
2114.1.22 Appliances required to be vented: Appliances
shall be connected to a listed venting system or provided
with other means for exhausting the flue gases to the
outside atmosphere in accordance with the venting system
selection chart contained in the Mechanical Code listed
in Appendix A.
2114.1.23 Exemption: Connections to vent systems shall
not be required for appliances of such size or character
that the absence of such connection does not constitute
a hazard to the fire safety of the building or its occupants.
The following appliances are not required to be vented
unless so required by their listing:
(1) Listed gas ranges;
(2) Built-in domestic cooking units listed and marked
as unvented units;
(3) Listed hot plates and listed laundry stoves;
(4) Listed domestic clothes dryers;
(5) Listed gas refrigerators;
(6) Counter appliances;
(7) Space (room) heaters listed for unvented use, only
upon prior approval by the Building Official;
(8) Specialized equipment of limited input such as
laboratory burners or gas lights; and
(9) Electric appliances.
When any or all of the appliances listed in items (5),
(6) and (7) above are installed so that the aggregate
input rating exceeds 30 British Thermal Units (BTU's)
per hour per cubic foot of room or space in which they
are installed, one or more of them shall be vent connected
or provided with approved means for exhausting the vent
gases to the outside atmosphere so that the aggregate
input rating of the remaining unvented appliance does
not exceed 30 BTU's per hour per cubic foot of room
or space in which they are installed. Where the room
or space in which they are installed is directly connected
to another room or space by a doorway, arch, or other
opening of comparable size, which cannot be closed,
the volume of such adjacent room or space may be included
in the calculations.
2114.1.24 Fireplaces and solid-fuel-burning appliances:
2114.1.25 General: Fireplaces, barbecues, smoke chambers,
solid-fuel-burning appliances and fireplace chimneys
shall be constructed of solid masonry, reinforced concrete
or other approved materials and shall conform to the
requirements of this section.
2114.1.26 Construction: Structural walls of fireplaces
shall be at least eight inches thick. Where a lining
of low-duty refractory brick (ASTM C64) or the equivalent,
at least two inches thick laid in fire-clay mortar (ASTM
C105, medium-duty) or its equivalent, or other approved
lining is provided, the total thickness of back and
sides, including the lining, shall be not less than
eight inches. Where such lining is not provided, the
thickness of the back and sides shall be not less than
12 inches. The firebox shall be 20 inches in depth and
will be permitted to be open on all sides, provided
that all fireplace openings are located within one room.
All factory-built fireplaces, freestanding fireplaces,
suspended factory-built fireplaces, solid-fuel-burning
radiant-type or circulating-type stoves or heaters,
liquid or gas fuel heaters or stoves, or electrically
heated stoves or heaters must be listed and approved
by one or more of the following:
(1) Underwriters' Laboratories, Inc.
(2) Building Officials Code Administration.
(3) Southern Building Code Congress.
(4) International Conference of Building Officials.
(5) Factory Mutual Research Corp.
The installation of all heating units must be in accordance
with the instructions and listing. Compliance may be
determined by the presence of a label from the approval
agency affixed on the appliance or accessory stating
that the appliance or accessory complies with nationally
recognized fire safety and requirements.
2114.1.27 Lining: Unlined masonry chimneys for use
with airtight and high efficiency solid-fuel-burning
stoves, heaters or fireplaces shall be prohibited.
2114.1.28 Existing masonry fireplace: Where a solid-fuel-burning
appliance is intended for installation into an existing
masonry fireplace with an unlined masonry chimney, an
approved listed metal liner shall be installed into
the existing unlined masonry chimney.
2114.1.29 Existing refractory-lined fireplace: Where
a solid-fuel-burning appliance is intended for installation
in front of an existing refractory-lined fireplace,
the entire front of the fireplace must be completely
sealed off with masonry or its equivalent. The opening
for the solid-fuel-burning appliance connector shall
penetrate the fireplace masonry chimney at a point above
the fireplace and into the liner. A solid-fuel-burning
appliance may be installed in front of an existing fireplace
with a refractory-lined chimney, provided that a tight-fitting
metal shield of at least twenty-four-gauge steel is
installed into the fireplace below the fireplace damper.
The opening cut into the metal shield shall not be larger
than the stack of the solid-fuel-burning appliance.
The metal stack shall extend into the fireplace to a
point where the damper, when closed, will rest completely
across the open end of the metal stack.
2114.1.30 Metal liners: Metal liners shall be provided
with spark-arrester-type, screened metal flashing caps.
The wire mesh openings in the flashing caps shall not
exceed more than 5/8 inch or less than 5/16 inch.
2114.1.31 Distance: The distance between a masonry
fireplace and combustibles shall be at least four inches,
and such combustibles shall not be placed within six
inches of a masonry fireplace opening. Wood facings
or trim normally placed around the fireplace opening
may be permitted when conforming to the requirements
of this section. However, such facing or trim shall
be furred out from the fireplace wall at least four
inches and attached to noncombustible furring strips.
The edges of such facings or trim shall be covered with
a noncombustible material. Where the wall of the masonry
fireplace are 12 inches thick, the facings or trim may
be attached directly to the masonry fireplace.
Solid-fuel-burning freestanding fireplaces, factory-built
fireplaces, suspended fireplaces, solid-fuel-burning
radiant-heat-type stoves or heaters shall be installed
at least 36 inches away from any combustible wall and
ceiling. Solid-fuel-burning circulating-heat-type stoves
or heaters shall be installed at least 12 inches away
from any combustible wall or ceiling. The distance away
from any combustible wall and ceiling may be reduced
by the installation of one-fourth inch masonry or millboard,
or twenty-eight-gauge sheet metal spaced out one inch
from the combustible wall and ceiling as specified in
the table below:
MINIMUM CLEARANCES FROM
COMBUSTIBLE WALLS AND CEILINGS
Stove Type
Radiant Circulating
Type of Protection (inches) (inches)
None 36 12
One-fourth-inch masonry or millboard, 18 6
spaced out 1 inch
Twenty-eight-gauge sheet metal, 12 4
spaced out 1 inch
Twenty-eight-gauge sheet metal 12 4
on one-eighth-inch masonry
or millboard, spaced out 1 inch
2114.1.32 Chimney connectors (stove pipes): The passage
of an uninsulated chimney connector or stove pipe through
a ceiling, floor or roof shall be prohibited.
The internal cross-sectional area of a chimney connector
shall not be less than that of the flue collar of the
solid-fuel- burning appliance.
The chimney connector shall be as short as possible
with not more than two ninety-degree elbows or their
equivalent.
The horizontal section of a chimney connector shall
have a rise of at least 1/4 inch for each foot of horizontal
pipe from the solid-fuel-burning appliance to the chimney.
The use of a Type B vent as a chimney connector or
as a chimney in connection with a solid-fuel-burning
appliance is prohibited.
All chimney connectors used with solid-fuel-burning
appliances shall be constructed on corrosion-resistant
steel with the following minimum diameters and gauge
of steel:
Connector Diameter
(inches) Steel Gauge
10 or less 24
Over 10 but less than 14 22
Over 14 but less than 16 20
16 and over 16
The chimney connector for a solid-fuel-burning appliance
shall be installed at least 18 inches away from any
combustible wall and ceiling. The clearance from a combustible
wall and ceiling may be reduced by the installation
of a one-fourth inch millboard or twenty-eight-gauge
sheet metal spaced out one inch from the combustible
wall and ceiling as specified in the table below:
MINIMUM CLEARANCE
FROM COMBUSTIBLE WALLS AND CEILINGS
Stove Pipe
Type of Protection (inches)
None 18
One-fourth-inch masonry or 18
millboard nailed to wall
One-fourth-inch masonry or 12
millboard spaced out 1 inch
One-fourth-inch masonry or 12
millboard covered with twenty-gauge
sheet metal
Twenty-gauge sheet metal spaced 9
out 1 inch
Twenty-gauge sheet metal over one- 9
fourth-inch masonry or millboard
spaced out 1 inch
The following four methods shall be considered as acceptable
for the passage of a chimney connector through a combustible
wall:
(1) Use an Underwriters' Laboratories, Inc. listing
all-fuel thimble extending through the wall with the
wall hole four inches larger than the thimble diameter.
The four-inch space between the thimble and the combustible
wall shall be filled with a noncombustible insulation.
(2) Use a ventilated thimble that is at least three
times larger in diameter than the chimney connector.
(3) Use a fire clay thimble surrounded by at least
eight inches of masonry or other noncombustible material.
(4) Use no thimble, but remove all of the combustible
wall within 18 inches on all sides of the chimney connector.
The eighteen-inch opening shall be closed in with a
noncombustible insulating material.
2114.1.33 Fire stopping: Combustible framing shall
be trimmed not less than two inches away from all masonry
chimneys and properly fire-stopped with a noncombustible
material to prevent the free travel of heat, flame and
smoke. When an approved, listed factory-built chimney
passes through a floor, ceiling or roof, an approved,
listed fire-stop spacer shall be installed to center
the factory-built chimney and provide the proper clearance.
The fire-stop spacer opening shall be tightfitting with
the approved, listed factory-built chimney to prevent
the free travel of heat, flame or smoke.
2114.1.34 Support: All masonry fireplaces shall be
supported on foundations designed in conformity with
Section 1006.0.
The installation of a solid-fuel-burning appliance
over an unprotected combustible floor shall be prohibited.
A combustible floor under a solid-fuel-burning appliance
shall be protected by one of the following means:
(1) Approved stove boards on mats.
(2) Mortared slate, brick or stone.
(3) Slate, brick or stone placed on top of continuous
noncombustible material.
The noncombustible protection over the combustible
floor shall extend at least 18 inches beyond the front,
rear or sides of the solid-fuel-burning appliance from
which the ashes are removed. The noncombustible floor
shall extend at least 12 inches beyond the sides, front
or rear of the solid-fuel-burning appliance that is
not used for the removal of ashes.
There shall be a continuous four-inch air space between
the bottom of the solid-fuel-burning appliance and the
protected floor.
2114.1.35 Screens: Screens or other approved protection
shall be installed on all openings for all fireplaces
and all other solid-fuel-burning appliances.
2114.1.36 Other types of fireplaces and solid-fuel-burning
stoves and heaters:
Fireplaces, factory-built fireplaces and solid-fuel-burning
stoves or heaters nonconforming to this code shall be
prohibited.
An approved, listed solid-fuel-burning appliance which
is also approved and listed to burn coal or its equivalent
shall be provided with approved, listed flue liners,
chimney connectors and grates.
2114.1.37 Solid or liquid waste: Burning of any solid
or liquid waste in a fireplace, stove or heater shall
be prohibited. When an approved, listed solid or liquid
waste heating system is intended for installation, approval
must be obtained from the Department of Environmental
Resources prior to the installation of the system.
T. Section 2119.0 shall provide as follows:
2119.0 Incinerators:
2119.1.1 Mechanical Code: Incinerators of all types
shall be installed in accordance with the applicable
provisions of the Mechanical Code listed in the Appendix.
2119.1.2 Construction of metal ducts and vents:
2119.1.3 Mechanical code: All metal vents, ducts and
duct systems required under the provisions of this article
for heating systems and equipment, and under the provisions
of Article 7 for ventilating and air-conditioning systems
shall be constructed and installed in accordance with
the requirements of the Mechanical Code listed in Appendix
A.
2119.1.4 Construction of ducts: Ducts and plenums may
be constructed of approved material constructed in accordance
with the requirements of the Mechanical Code listed
in Appendix A. Non-metallic ducts shall be constructed
and installed in accordance with their approval and
the applicable standards listed in Appendix A. Aluminum
ducts shall not be used in equipment rooms with fuel-fired
equipment, encased in or under concrete slabs on grade,
for kitchen or fume exhausts or in systems where air
entering the duct is over 250 F.
2119.1.5 Spark arrestors:
2119.1.6 Mechanical code: All chimneys, stacks and
flues, including incinerator stacks, which emit sparks
shall be provided with a spark arrestor conforming to
the requirements of the Mechanical Code listed in Appendix
A.
U. Section 3500.0 shall provide as follows:
3500.0 Referenced standards:
3500.1 Zoning Law: In no event shall the provisions
of this article be deemed to authorize construction
in violation of the requirements of Ordinance No. 1753,
as amended, the Township of Abington Zoning Ordinance.EN
Should the provisions of the Zoning Ordinance be more
restrictive than those of this article, it shall control.
Should the provisions of this article be more restrictive
than those of the Zoning Ordinance, this article shall
control.
V. Section 2200.0 shall provide as follows:
2200.1 Scope: The design and installation of plumbing
systems, including sanitary and storm drainage facilities,
water supplies and stormwater and sewage disposal in
buildings shall comply with the requirements of this
article and the Township of Abington Plumbing Code,
Chapter 121 of the Code of the Township of Abington.
W. Section 2201.1 shall provide as follows:
2201.1 When required: Prior to the issuance of any
permit, plumbing plans and specifications for the installation,
alteration or addition to the plumbing system of any
building, structure or premises shall be submitted to
the Township of Abington, Department of Code Enforcement,
Plumbing Division, in accordance with the Requirements
of Chapter 121 of the Code of the Township of Abington.
X. Section 3500.2: Delete entire Chapter 29.
Y. Section 3500.3. shall provide as follows:
3500.3 Scope: The design and installation of plumbing
systems, including sanitary and storm drainage facilities,
water supplies and stormwater and sewage disposal in
buildings shall comply with requirements of the Township
of Abington Plumbing Code, Chapter 121 of the Code of
the Township of Abington.
Z. Section 3500.4 shall provide as follows:
3500.4 Plans required: Prior to the issuance of any
permit, plumbing plans and specifications for the installation,
alteration or addition to the plumbing system of any
building, structure or premises shall be submitted to
the Township of Abington Department of Code. Enforcement
(Plumbing Division) in accordance with the requirements
of Chapter 121 of the Code of the Township of Abington.
AA. Section 3500.5 shall provide as follows:
3500.5 By reference, this ordinance adopting the BOCA
Basic Building Code/1996, Thirteenth Edition, also references
and adopts the BOCA Basic Fire Prevention Code/1996.
BB. Section 3500.6 shall provide as follows:
3500.6 By reference, this ordinance adopting the BOCA
Basic Building Code/1996, Thirteenth Edition, also references
and adopts the Township of Abington Electrical Ordinance
(Ordinance No. 1480).
CC. Section 3500.7 shall provide as follows:
3500.7 By reference, this ordinance adopting the BOCA
Basic Building Code/1996, Thirteenth Edition, also references
and adopts the BOCA Mechanical Code/1996 Edition.
62-3. (Reserved)
ARTICLE II, Dangerous Buildings [Adopted 7-13-1989
by Ord. No. 1661]
62-4. Definitions.
As used in this article, the following terms shall
have the meanings indicated, unless a different meaning
clearly appears from the context:
BUILDING -- A structure resting on its own foundation.
DANGEROUS BUILDING -- All buildings, dwellings or dwelling
units which have any or all of the following defects
shall be deemed a "dangerous building" and
constitute a threat to the health, safety or welfare
of the public:
A. Those whose interior walls or other vertical structural
members list, lean or buckle to such an extent that
a plumb line passing through the center of gravity falls
outside of the middle third of its base.
B. Those which, exclusive of the foundation, show damage
or deterioration to 33% of the supporting member or
members or damage or deterioration to 50% of the nonsupporting
enclosing or outside walls or covering.
C. Those which have improperly distributed loads upon
the floors or roofs or in which the same are overloaded
or which have insufficient strength so as to be structurally
safe for the purposed use.
D. Those which have been damaged by fire, wind or other
causes so as to be dangerous to life, safety or the
general welfare of the occupants or the public.
E. Those which are so damaged, dilapidated, decayed,
unsafe, unsanitary or vermin-infested so as to be unfit
for human habitation or are likely to cause sickness
or disease so as to work injury to the health, safety
or general welfare of those living therein.
F. Those which have parts thereof which are so attached
that they may fall and injure property or members of
the public.
G. Those which lack illumination, ventilation or sanitation
facilities or because of another condition are unsafe,
unsanitary or dangerous to the health, safety or general
welfare of the occupants or the public.
H. Those which, because of their locations, are unsanitary
or otherwise dangerous to the health, safety or welfare
of the occupants or the public.
I. Those existing in violation of any provision of
the Building Code, Fire Prevention Code or other ordinances
of the Township of Abington or which by reason of an
illegal use or occupancy shall be deemed dangerous to
life and health.
DWELLING -- Any building which is wholly or partly
used or intended to be used for living or sleeping by
human occupants.
DWELLING UNIT -- Any room or group of rooms located
within a dwelling and forming a single habitable unit
with facilities which are used or intended to be used
for living or sleeping by human occupants. Whenever
the words "dwelling" or "dwelling unit"
are used in this article, they shall be construed as
though they were followed by the words "or any
part thereof."
OWNER -- A person who, alone or jointly or severally
with others, shall have legal title to any dwelling,
dwelling unit or structure as owner or agent of the
owner or as executor, executrix, administrator, administratrix
or guardian of the estate of the owner. Any such person
thus representing the actual owner shall be bound to
comply with the provisions of this article and, with
rules and regulations adopted pursuant thereto, to the
same extent as if he were the owner.
PERSON -- Any individual, firm, corporation, association
or partnership or other legal entity.
62-5. Declaration of nuisance.
All dangerous buildings within the terms of 62-4 of
this article are hereby declared to be public nuisances
and shall be repaired, vacated or demolished as herein
provided.
62-6. Guidelines for repair, vacation or demolition.
The following guidelines shall be followed by the Code
Enforcement Officer of the Township of Abington in ordering
repair, vacation or demolition:
A. If the dangerous building can reasonably be repaired
so that it will no longer exist in violation of the
terms of this article, it shall be ordered to be repaired.
B. If the dangerous building is in such condition as
to make it dangerous to the health, safety or general
welfare of its occupants and is so placarded, it shall
be ordered to be vacated within such length of time,
not exceeding 30 days, as is reasonable.
C. No dwelling or dwelling unit which has been placarded
as unfit for human habitation shall again be used for
human habitation until written approval is secured from
and such placard is removed by the Code Enforcement
Officer. The Code Enforcement Officer shall remove such
placard whenever the defect or defects upon which the
placarding action was based have been corrected so as
to comply with the requirements of the Code of the Township
of Abington.
D. If a dangerous building is 50% or more damaged or
decayed or deteriorated from its original condition
so as to be structurally unsound or if a dangerous building
cannot be repaired so that it will no longer exist in
violation of the terms of this chapter or any ordinance
of the Township of Abington or statute of the Commonwealth
of Pennsylvania and is in impending danger of collapse,
it shall be ordered to be demolished.
62-7. Duties of Enforcement Officer.
A. The Code Enforcement Officer shall inspect on a
regular basis dwellings and buildings to determine whether
any conditions exist which render such premises as dangerous
buildings within the terms of 62-4 above.
B. Whenever an inspection discloses that a building
is dangerous and thus has become a public nuisance,
the Code Enforcement Officer shall issue a written notice
to the owner, agent of the owner or occupant of such
dwelling or building. The notice:
(1) Shall be in writing.
(2) Shall include a statement of the reasons it is
being issued.
(3) Shall state a reasonable time to rectify the conditions
constituting the nuisance or to remove and demolish
the building.
(4) May contain an outline of the remedial action required
on the dwelling or building.
(5) Shall state that all work to be performed on the
building shall be in conformance with the requirements
of the Code of the Township of Abington.
(6) Shall state that failure to rectify the conditions
constituting the nuisance within the time specified
shall constitute a violation of this article and shall
enable the Township of Abington to take the necessary
remedial action of repair, removal or demolition and
collect the cost of such action from the owner, agent
of the owner or occupant of the dangerous building as
provided by law for the recovery of municipal claims.
(7) Shall be served upon the owner, agent of owner
or occupant.
(a) Except in emergency cases, all notices shall be
deemed to be properly served upon the owner if a copy
thereof is served upon that person individually or sent
by registered mail to the last known address and if
a copy thereof is posted in a conspicuous place in or
about the dwelling or building affected by the notice.
(b) Except in emergency cases, when the owner, agent
of the owner or occupant is absent from the Township
of Abington, all notices or orders provided for herein
shall be sent by registered mail to the owner, agent
of the owner and occupant, as shown by the records of
the County Recorder of Deeds, to the last known address
of each, and a copy of such notice shall be posted in
a conspicuous place on the dangerous dwelling or building
to which it relates. Such mailing and posting shall
be deemed adequate service.
C. The Code Enforcement Officer shall appear at all
hearings conducted by the Code Enforcement Committee
and testify as to the condition of dangerous buildings.
62-8. Hearings.
A. The owner, agent of the owner or occupant of a dangerous
building served with notice in connection with the enforcement
of any provision of this article may request and shall
be granted a hearing on the matter before the Code Enforcement
Committee, provided that such person shall file with
the Code Enforcement Officer a written petition requesting
such hearing and setting forth a brief statement of
the grounds therefor within 10 days after the day the
notice was served or posted. Upon receipt of such petition,
the Code Enforcement Officer shall set a time and place
for such hearing and shall give the petitioner written
notice thereof. At such hearing the petitioner shall
be given an opportunity to be heard and to show why
such notice should be modified or withdrawn. The hearing
shall be commenced not later than 30 days after the
day on which the petition was filed.
B. After such hearing, the Code Enforcement Committee
shall sustain, modify or withdraw the notice. If the
Code Enforcement Committee sustains or modifies such
notice, it shall be deemed to be an order. Any notice
served pursuant to this article shall automatically
become an order if a written petition for a hearing
is not filed with the Code Enforcement Officer within
10 days after such notice is served.
62-9. Removal of notice prohibited.
No person shall remove or deface the posted notice
of a dangerous dwelling or building.
62-10. Emergency cases.
Whenever the Code Enforcement Officer finds that an
emergency exists which requires immediate action to
protect the public health or safety, he may, without
notice or hearing, issue an order reciting the existence
of such an emergency and requiring that such action
be taken as is necessary to meet the emergency. Notwithstanding
the other provisions of this article, such order shall
be effective immediately. Any person to whom such order
is directed shall comply therewith immediately, but
upon petition to the Code Enforcement Officer shall
be afforded a hearing with the Code Enforcement Committee
as soon as possible. After such hearing, depending upon
the findings as to whether the provisions of this article
have been complied with, the Code Enforcement Officer
shall continue such order in effect or modify or revoke
it. The costs of any emergency repair, vacation or demolition
of a dangerous building shall be collected in the same
manner as provided herein for the other cases.
62-11. Abatement by township.
Should the owner, agent of the owner or occupant of
a dangerous dwelling or building fail to comply with
an order of the Code Enforcement Officer within 30 days
of service of the notice issued by the Code Enforcement
Officer, the Code Enforcement Officer shall cause such
building or structure to be repaired, vacated or demolished,
as the facts may warrant, under the standards hereinbefore
provided. The Township of Abington may collect the cost
of such repair, vacation or demolition, including interest
as provided by law for the recovery of municipal claims.
62-12. Recovery of costs.
A. Upon completion by the Township of Abington of all
work necessary to repair, vacate or demolish any dangerous
building, the Township shall send a bill of assessment
to the registered owner, agent of the owner or occupant
at the last known address setting forth the date of
original notice to the owner advising him of the dangerous
condition of the building, the kind and character of
the work performed, the date of completion of the work
by the township and the cost incurred by the township.
B. The Board shall notify the registered owner of the
property that he or she must pay the assessment amount
within 30 days after the mailing of the bill of assessment
and that failure to make such payment will require the
township to file a municipal lien upon the property
of the delinquent owner and to proceed to execute upon
such lien with notice to the owner and lien creditors
as may be required by law.
62-13. Violations and penalties.
Any person who shall violate any provision of this
article shall be subject to enforcement proceedings
before the District Justice as set forth in the Pennsylvania
Municipalities Planning Code. Any person found to be
in violation of the provision of this article shall
be liable to pay a judgment not to exceed $500, plus
court costs, including reasonable attorney's fees incurred
by the Township of Abington. Each day that a violation
continues shall constitute a separate violation.
ARTICLE III, CABO One and Two Family Dwelling Code
[Adopted 4-11-1996 by Ord. No. 1761]
62-14. Adoption of standards.
The Board of Commissioners of the Township of Abington
does hereby enact and ordain by adoption the CABO One
and Two Family Dwelling Code/1992 Edition, as published
by the Council of American Building Officials and the
whole thereof, except such portions that are deleted,
modified, amended or added by this chapter, which is
on file in the office of the Secretary of the Township
of Abington. The same is hereby adopted and incorporated
as fully as if set out at length herein, and, from the
date on which this chapter takes effect, the provisions
thereof shall be controlling within the limits of the
Township of Abington.
62-15. Amendments to standards.
The CABO One and Two Family Dwelling Code/1992 Edition,
is amended as noted:
A. Section R-106.3, Penalty, shall read as follows:
R-106.3 Penalty: Any person, firm or corporation violating
any of the provisions of this code shall be guilty of
a misdemeanor and, upon conviction for any such violation,
shall pay a fine of not more than $1,000 or be imprisoned
for not more than 30 days, or both. Each day or portion
thereof that the violation continues shall constitute
a separate violation and shall bear a like penalty.
B. Appendix B: In place of Tables, insert Span Chart.
|