|

Code Book
Code of the Township of Abington
[ Back
to Table of Contents ]
 |
|
Search This Page
Type in the text you wish to locate on this
page (press the "Find" button
again or "Alt +S" to continue
the search and find the next instance of
the word you are looking for):
|
|
 |
PART II GENERAL LEGISLATION: Chapter 85, FIRE
PREVENTION
[HISTORY: Adopted by the Board of Commissioners of
the Township of Abington 4-8-1971 by Ord. No. 1305.
Amendments noted where applicable.]
GENERAL REFERENCES
Fire Department -- See Ch. 12.
Fire police force -- See Ch. 14.
Alarm systems -- See Ch. 56.
Building construction -- See Ch. 62.
Burning -- See Ch. 65.
Housing standards -- See Ch. 98.
85-1. Adoption of code by reference. [Amended 10-11-1990
by Ord. No. 1684]
There is hereby adopted by the Township of Abington,
for the purpose of prescribing regulations governing
conditions hazardous to life and property from fire
or explosion, that certain code known as the "BOCA
National Fire Prevention Code/1990," Eighth Edition,
and the whole thereof, including all appendices, as
published by the Building Officials and Code Administrators
International, Inc., save such portions that are hereafter
deleted, modified or amended, of which code not fewer
than one copy has been and now is filed in the office
of the Secretary of the Township of Abington at 1176
Old York Road, Abington, Pennsylvania, and the same
is hereby adopted and incorporated as fully as if set
out at length herein, and the provisions thereof shall
be controlling within the limits of the Township of
Abington, Montgomery County, Pennsylvania.
85-2. Definitions. [Amended 3-8-1973 by Ord. No. 1346]
A. Whenever the following words are used in this chapter
and in the Fire Prevention Code or any part thereof,
they shall have the respective meanings as follows:
ALARM SERVICE -- The service required following the
manual operation of a fire alarm box, the transmission
of an alarm indicating the operation of protective systems,
including heat, smoke, water flow, or the transmission
of an alarm from other protective systems. [Added 6-13-1974
by Ord. No. 1377]
ANIMAL HOSPITAL -- Any building under the supervision
of a veterinarian, used for the medical or surgical
treatment, housing or boarding of small domestic animals
such as dogs, cats, rodents, birds or fowl. [Added 5-11-1989
by Ord. No. 1657]
ANIMAL KENNEL -- Any building or buildings used for
the housing, boarding, grooming or manicuring of small
domestic animals such as dogs, cats, rodents, birds
or fowl. [Added 5-11-1989 by Ord. No. 1657]
APARTMENT -- A dwelling unit within a multiple dwelling.
This classification includes apartments in apartment
houses, apartment hotels, bachelor apartments, studio
apartments and kitchenette apartments. [Added 5-11-1989
by Ord. No. 1657]
APARTMENT HOUSE -- A building arranged, intended or
designed to be occupied by three or more families living
independently of each other. [Added 5-11-1989 by Ord.
No. 1657]
APPROVED RATING BUREAU -- A fire insurance rating and/or
inspection bureau, department, organization or agency,
including inter alia, American Insurance Association,
Factory Mutual Fire Insurance Companies, Industrial
Risk Insurers, Improved Risk Mutuals, Insurance Service
Office or any other such organization duly approved
by resolution of the Board of Commissioners. [Amended
5-11-1989 by Ord. No. 1657]
APPROVED SPRINKLER SYSTEM -- An improved sprinkler
system, for fire protection purposes, is an integrated
system of underground and overhead piping designed in
accordance with fire protection engineering standards,
including water supply systematic pattern of piping
valves and actuating devices as prescribed by the National
Fire Protection Association or any other recognized
engineering association that is accepted by an approved
fire insurance rating bureau, department or organization.
[Amended 5-11-1989 by Ord. No. 1657]
AUTO BODY SHOP -- Any structure or any building or
part thereof that is used for the repair, spraying or
painting of vehicle bodies, chassis, wheels, fenders,
bumpers and/or accessories of automobiles and other
vehicles or conveyances. [Added 5-11-1989 by Ord. No.
1657]
AUTOMATIC FIRE DETECTORS -- An individual device or
devices designed to detect flame, heat, smoke or other
combustion gases resulting from a fire and to automatically
operate electrical signaling contacts. The signaling
contacts may be integral parts of an individual device
or parts of a separate device to which the detecting
element is connected as an extended component. [Added
6-13-1974 by Ord. No. 1377]
AUTOMOBILE SERVICE STATION -- Any area of land, including
any structures thereon, or any building or part thereof
that is used for the retail sale of gasoline, diesel
or other fuel, kerosene, oil or accessories for motor
vehicles and which may include facilities used for polishing,
greasing, washing, dry cleaning or otherwise cleaning
or servicing such vehicles, including self service or
full serve filling stations, but not including the storage
of motor vehicles. [Added 5-11-1989 by Ord. No. 1657]
BASEMENT -- A story partly underground but having at
least 1/2 of its height above the mean level of the
adjoining ground. A basement shall be counted as a story
for the purpose of height measurement if the vertical
distance between the ceiling of the basement and the
mean level of the adjoining ground is more than five
feet or is used for business or dwelling purposes other
than a game or recreation room. [Amended 5-11-1989 by
Ord. No. 1657]
BUILDING -- Any structure having a roof supported by
columns or walls and intended for the shelter, housing
or enclosure of persons, animals or chattels, and including
integral covered porches or bay windows and chimneys.
[Added 5-11-1989 by Ord. No. 1657]
BUILDING, DETACHED -- A structure surrounded by open
space on the same lot as the main building. [Added 5-11-1989
by Ord. No. 1657]
BUILDING OFFICIAL -- Building Inspector or the Building
Inspector's Assistants of the Township of Abington,
Montgomery County, Pennsylvania.
CELLAR -- A story, 1/2 or more of which is below grade.
CENTRAL STATION SUPERVISORY SYSTEM -- A system or group
of systems, the operations of which are signaled to,
recorded in, maintained and supervised from an approved
central station in which there are competent and experienced
observers and operators in attendance at all times whose
duty it shall be, upon receipt of a signal, to take
such action as shall be required under the rules established
for their guidance. Such systems shall be controlled
and operated by a person, firm or corporation whose
principal business is the furnishing and maintaining
of supervised protective signaling service and who has
no professional or business interest in the protected
properties. [Added 6-13-1974 by Ord. No. 1377]
CHIEF OF THE BUREAU OF FIRE PREVENTION -- Fire Marshal
of the Township of Abington, Montgomery County, Pennsylvania.
CLOUD CHAMBER SMOKE DETECTOR -- A form of sampling
detector in which the air pump draws a sample of air
into a high-humidity chamber within the detector. After
the air is in the humidity chamber, the pressure is
lowered slightly. If smoke particles are present, the
moisture in the air condenses on them, forming a cloud
in the chamber. The density of this cloud is then measured
by the photoelectric principle. When the density is
greater than a predetermined level, the detector responds
to the smoke. [Added 10-12-1978 by Ord. No. 1474]
CLUBS, LODGES, FRATERNAL ORGANIZATIONS -- Any establishment
operated for social, recreational or educational purposes
but open only to members and not to the general public.
[Added 5-11-1989 by Ord. No. 1657]
CODE OFFICIAL -- The Fire Marshal of the Township of
Abington, Montgomery County, Pennsylvania. [Added 10-11-1990
by Ord. No. 1684]
COMMAND STATION -- A cutoff fire-resistive room located
on the ground floor, containing all the equipment necessary
during emergencies to control elevators, communication
systems, alarms, detectors and other necessary equipment
for complete control of fire fighting and evacuation.
COMMERCIAL -- All structures for wholesale or retail,
including, inter alia, department stores, supermarkets,
shopping centers, shopping malls, marts, all builders
supply stores, home improvement centers; furniture,
clothing and appliance stores, all off-premises storage
and warehouse structures used in whole or in part for
commercial storage; restaurants, bakeries, delicatessens,
donut shops, cafeterias, ice-cream parlors, banquet
or private catering, fast-food restaurants, pizza parlors,
steak and hoagie houses, pharmacies and sporting goods;
specialty stores, including inter alia, shoe or leather
repair, beauty or nail salons, laundry or dry cleaners,
jewelry or watch repair. [Added 5-11-1989 by Ord. No.
1657]
COMMISSIONERS -- Commissioners of the Township of Abington,
Montgomery County, Pennsylvania.
COMMUNITY CENTER -- A meeting place used by members
of a community for social, cultural, educational or
recreational purposes. [Added 5-11-1989 by Ord. No.
1657]
COMPARTMENTATION -- An area of refuge within a building
for the building's occupants. [Added 6-13-1974 by Ord.
No. 1377]
CORPORATION COUNSEL -- Solicitor of the Township of
Abington, Montgomery County, Pennsylvania.
CRAWL SPACE -- That part of a building that is below
grade but is less than six feet in height.
DEPARTMENT OF PUBLIC SAFETY -- Department of Public
Safety of the Township of Abington, Montgomery County,
Pennsylvania.
DWELLING -- A building or structure designed for living
quarters for one or more families, including modular
or prefabricated homes which are supported by a foundation
or are otherwise permanently attached to the land, but
not including hotels, rooming houses or other accommodations
used for transient occupancy. [Added 5-11-1989 by Ord.
No. 1657]
DWELLING, MULTIFAMILY -- A building used by three or
more families living independently of each other and
doing their own cooking, including apartment houses,
row houses and townhouses. [Added 5-11-1989 by Ord.
No. 1657]
DWELLING, SINGLE-FAMILY DETACHED -- A building used
by one family having only one dwelling unit and having
two side yards. [Added 5-11-1989 by Ord. No. 1657]
DWELLING, SINGLE-FAMILY SEMIDETACHED -- A building
used by one family having one side yard, and one parapetted
masonry party well in common with another building (twin).
[Added 5-11-1989 by Ord. No. 1657]
DWELLING, TWO-FAMILY DETACHED -- A building used by
two families, with one dwelling unit arranged over the
other and having two side yards. [Added 5-11-1989 by
Ord. No. 1657]
DWELLING, TWO-FAMILY SEMIDETACHED -- A building used
by two families, with one dwelling unit arranged over
the other, having one side yard and one parapetted masonry
party well in common with another building. [Added 5-11-1989
by Ord. No. 1657]
DWELLING UNIT -- One or more rooms used for living
and sleeping purposes and having a kitchen with fixed
cooking facilities arranged for occupancy by one family.
[Added 5-11-1989 by Ord. No. 1657]
EDUCATIONAL -- All schools, including, inter alia,
private, public, parochial, religious, organizational,
vocational, technical, business, military, trade school,
pre-school, kindergarten, grade school, junior high
school, senior high school, preparatory schools, colleges,
universities and all structures within the complex.
[Added 5-11-1989 by Ord. No. 1657]
FAMILY -- One or more persons related by blood, adoption
or marriage, or not more than two unrelated persons
living and cooking together as a single housekeeping
unit. [Added 5-11-1989 by Ord. No. 1657]
FAMILY LIVING UNIT -- That structure, area or room
or a combination of rooms in which a family or individual
lives. This is meant to cover living area only and not
common usage areas in multifamily buildings, such as
corridors, lobbies, basements, etc. [Added 10-12-1978
by Ord. No. 1474]
FIRE OFFICIAL -- Fire Marshal of the Township of Abington,
Montgomery County, Pennsylvania.
FIRE RESISTIVE BUILDING -- A structure with structural
designs employing reinforced concrete or conventional
protected steel beam, girder and columns construction
or only such materials and designs as would warrant
not less than a four-hour fire-resistant rating for
main load-bearing walls, columns and girders and their
supporting members. The standard three-hour fire-resistant
rating is given to floors constructed of reinforced
concrete or its equivalent at least four inches thick
for load-bearing floors and three inches in thickness
for roof when supporting none other than its own load.
[Amended 5-11-1989 by Ord. No. 1657]
FLAME DETECTOR -- A device which detects the infrared
or ultraviolet or visible radiation produced by fire.
[Added 10-12-1978 by Ord. No. 1474]
GARDEN APARTMENT -- A two-story multifamily dwelling
containing one story dwelling units under one ownership.
[Added 5-11-1989 by Ord. No. 1657]
HEAT DETECTOR -- A device which detects abnormally
a high temperature or rate-of-temperature rise. [Added
10-12-1978 by Ord. No. 1474]
HIGH-HAZARD OCCUPANCY -- A building or structure occupied
for the storage, manufacture, laundry and dry-cleaning
process or sales of highly combustible or explosive
products or materials which are likely to burn with
extreme rapidity or which may produce or emit poisonous
toxic or noxious alkalies, acid or other liquids or
chemicals involving flame, fume, explosive, poisonous,
irritant or corrosive cases; and the storage, process,
manufacture or sales of any products or materials involving
explosive mixtures of dust or which result in the division
of particulate matter into fine particles subject to
a dust explosion or spontaneous ignition. [Amended 5-11-1989
by Ord. No. 1657]
HIGH-RISE STRUCTURE -- All structures or buildings
in excess of six stories or 65 feet in height above
mean grade level. [Added 6-13-1974 by Ord. No. 1377]
HOSPITAL -- An institution providing health services,
primarily for in-patients, and medical or surgical care
of the sick or injured, including, as an integral part
of the institution, such related facilities as laboratories
out-patient departments, training facilities, central
service facilities and staff offices. [Added 5-11-1989
by Ord. No. 1657]
HOTEL OR MOTEL -- A building containing 10 or more
guest rooms or a group of such buildings specifically
designed for the temporary lodging of transient guests,
provided that no room shall have cooking facilities
of any kind. Such establishment shall make available
to the occupants customary hotel services such as room
service for food and beverages, maid service and the
furnishing and laundering of linen. [Added 5-11-1989
by Ord. No. 1657]
HOUSEHOLD -- The family living unit in single-family
detached dwellings, single-family attached dwellings,
multifamily buildings and mobile homes. [Added 10-12-1978
by Ord. No. 1474]
INDUSTRIAL -- All structures used for the manufacture
and/or assembly of wood, metal, electronic, animal,
natural, plastic, glass and synthetic products, processing
or food products, all off-premises storage and warehousing
of industrial raw supplies and finished products, paper
products, printing, book binding, photo engraving and
publishing. [Added 5-11-1989 by Ord. No. 1657]
INN -- A building containing fewer than 10 but more
than four guest rooms specifically designed for the
temporary lodging of transient guests, provided that
no room shall have cooking facilities of any kind. Such
establishment shall make available to the occupants
customary hotel services, such as room service for food
and beverages, maid service and the furnishing and laundering
of linen. [Added 5-11-1989 by Ord. No. 1657]
INSTITUTIONAL -- A building or a group of buildings
within an envelope with sleeping rooms where persons
are housed or lodged and furnished with meals and nursing
care dormitories and which is approved for nonprofit
agencies licensed for profit making operations by the
Pennsylvania Department of Public Welfare, including,
inter alia, all homes for the aged and/or retired; retirement
homes, apartments, townhouses, condominiums, rooms and
boarding for the aged and/or retired; hospitals, therapeutic
and prophylactic sanitariums; trauma centers and penal
institutions; group home care for the mentally or physically
handicapped; children's day nurseries and child-care
centers; schools, animal hospitals and kennels. [Added
5-11-1989 by Ord. No. 1657]
IONIZATION DETECTOR -- A device with a small amount
of radioactive material which ionizes the air in the
sensing chamber, thus rendering it conductive and permitting
a current to flow through the air between two electrodes.
This gives the sensing chamber an effective electrical
conductance. When smoke particles enter the ionization
area, they decrease the conductance of the air by attaching
themselves to the ions, causing a reduction in mobility.
When the conductance is less than a predetermined level,
the detector circuit responds. [Added 10-12-1978 by
Ord. No. 1474]
MERCANTILE -- Malls, retail and department stores and
commercial stores affiliated with retail. [Added 5-11-1989
by Ord. No. 1657]
MODIFIED FIRE-RESISTIVE BUILDING -- A structure employing
the same structural materials as fire-resistive building,
but with supports consisting of structural forms and/or
light steel members commonly referred to as "light
steel," "metal lumber," and "bar
joists," regardless of the fire-resistant ratings.
Prestressed concrete shall also be considered as modified
fire relative construction. Modified fire-resistive
construction shall be in general based on materials
and designs having not less than a three-hour fire-resistive
rating. [Added 5-11-1989 by Ord. No. 1657]
MODULAR OR PREFABRICATED HOME -- A detached single-family
dwelling designed and constructed at another location
and shipped complete, except for minor incidental unpacking
and assembly at a permanent location and set on a permanent
foundation. The utilities connection shall be in compliance
with the Building Code of the Township of Abington.EN
[Added 5-11-1989 by Ord. No. 1657]
MULTIPLE-STATION ALARM DEVICE -- Single-station devices,
two or more of which may be interconnected so that actuation
of one device causes all integral or separate audible
alarms to operate. It may also consist of one single-station
device having connections for other detectors or manual
stations. [Added 10-12-1978 by Ord. No. 1474]
MUNICIPALITY -- The Township of Abington, Montgomery
County, Pennsylvania.
NONCOMBUSTIBLE BUILDING -- A structure having masonry
walls and with floors and roof of noncombustible construction.
Metal walls with steel columns, beams, girders and roof
may be considered as a noncombustible or prefabricated
structure. [Added 5-11-1989 by Ord. No. 1657]
OFFICE -- A building designed or used primarily for
the affairs of a business, including, inter alia, professional
and engineering offices; realtors, financial, investment
and personal services offices; mental, physical medicine
and trauma treatment offices; municipal utilities, consultations,
referral or testing offices, post offices and banks.
No part of the building shall be used for manufacturing
or processing or for a dwelling other than for a watchman
or custodian. [Added 5-11-1989 by Ord. No. 1657]
PHOTOELECTRIC BEAM-TYPE DETECTOR -- A device that consists
of a light source which is projected across the area
to be protected into a photosensing cell. Smoke between
the light source and the receiving photosensing cell
reduces the light reaching the cell, causing actuation.
[Added 10-12-1978 by Ord. No. 1474]
PHOTOELECTRIC SPOT-TYPE DETECTOR -- A device that contains
a chamber with either overlapping or porous covers which
prevent the entrance of outside sources of light but
which allow the entry of smoke. The unit contains a
light source and a special photosensitive cell in the
darkened chamber. The cell is either placed in the darkened
area of the chamber at an angle different from the light
path or has the light blocked from it by a light stop
or shield placed between the light source and the cell.
With the admission of the smoke particles, light strikes
the particles and is scattered and reflected into the
photosensitive cell. This causes the photosensing circuit
to respond to the presence of smoke particles in the
smoke chamber. [Added 10-12-1978 by Ord. No. 1474]
PRODUCTS-OF-COMBUSTION DETECTORS -- A detecting combination
designed to detect one or more products of combustion.
These products may consist of gases, ions, water vapor,
invisible as well as visible smoke particles. [Added
6-13-1974 by Ord. No. 1377]
PUBLIC ASSEMBLY -- All buildings or areas within a
building used as churches, temples, synagogues, chapels
or other places of worship, including affiliated offices,
funeral homes, ceremonies and socials; theaters, auditoriums,
cinemas, operas, musicals, live performances, symphony
orchestras and bands; fraternal, religious, political,
patriotic, civic, cultural or private clubs, lodges
or organizations; arenas, rinks, amusement centers,
bowling alleys and courts; libraries, police and fire
stations; post offices, telephone and telegraph offices,
rail and bus terminals; YMCA community centers, radio
or television studios, art and dance studios or stations
with an audience accommodation. [Added 5-11-1989 by
Ord. No. 1657]
RESIDENTIAL -- A place where one or more persons live,
including, inter alia, all multifamily dwelling units
and single-family attached dwelling units; bachelor,
garden, kitchenette and studio apartments, hotels, motels,
inns, tourist or boarding houses; rectory convent, townhouses
and row homes. [Added 5-11-1989 by Ord. No. 1657]
RESISTANCE BRIDGE SMOKE DETECTOR -- A device that responds
to an increase of smoke particles and moisture, present
in products of combustion, which fall on an electrical
bridge grid. As these conductive substances fall on
the grid, they reduce the resistance of the grid and
cause the detector to respond. [Added 10-12-1978 by
Ord. No. 1474]
SAMPLING SMOKE DETECTOR -- A device that consists of
tubing distributed from the detector unit to the area(s)
to be protected. An air pump draws air from the protected
area back to the detector through the air-sampling ports
and piping. At the detector, the air is analyzed for
smoke particles. [Added 10-12-1978 by Ord. No. 1474]
SEPARATE SLEEPING AREAS -- The area or areas of the
family living unit in which the bedrooms or sleeping
rooms are located. Bedrooms or sleeping rooms separated
by other use areas, such as kitchens or living rooms,
but not bathrooms, shall be considered as separate sleeping
areas for the purposes of this chapter. [Added 10-12-1978
by Ord. No. 1474]
SINGLE AND SEPARATE OWNERSHIP -- The ownership of a
lot or contiguous lots by one or more persons, partnerships
or corporations which ownership is separate and distinct
from that of any abutting or adjoining it. [Amended
5-11-1989 by Ord. No. 1657]
SINGLE-STATION ALARM DEVICE -- An assembly incorporating
the detector, control equipment and the alarm-sounding
device in one unit, operated from a power supply either
in the unit or obtained at the point of installation.
[Added 10-12-1978 by Ord. No. 1474]
SMOKE DETECTOR -- A device which detects the visible
and invisible particles of combustion. [Added 10-12-1978
by Ord. No. 1474]
STORAGE FACILITIES -- Furniture and household goods,
lockers, vehicle and equipment lockers. [Added 5-11-1989
by Ord. No. 1657]
SUBSTANTIALLY ALTERED -- Any substantial structural
alteration in/or addition to the supporting or structural
members of a building or structure, such as bearing
columns, bearing beams or bearing girders, provided
that a substantial alteration shall not include, inter
alia, repairs to roof, walls or interior painting or
redecorating, elimination, relocation or construction
of nonbearing partitions within an existing structure,
repairs to air conditioning, repairs or replacement
of heating system(s), modernization of existing kitchens
or bathrooms, relocation or replacement of utility lines,
including gas, water, sewer or electricity. [Amended
5-11-1989 by Ord. No. 1657]
TOURIST OR BOARDING HOME -- A building where, for compensation,
lodging is provided for at least four guests but not
more than 10 guests on a temporary basis. [Added 5-11-1989
by Ord. No. 1657]
TREATED LUMBER -- Roofs of structures having masonry
walls may be accorded special treatment when the fire-retardent
roof deck is at least two inches thickness, and the
beam thickness is at least four inches in thickness,
identified by the Underwriter's Laboratories as having
a flame spread classification of not exceeding 25 inches
and showing no evidence of significant progressive production
when subjected to at least 30 minutes test duration.
The installation must be verified by the contractor.
[Added 5-11-1989 by Ord. No. 1657]
TOWNSHIP -- The Township of Abington, Montgomery County,
Pennsylvania.
VEHICLE PARKING OR STORAGE -- All vehicle parking or
storage structures, including, inter alia, all above
or below grade private or public vehicle parking or
storage structures or buildings; all open deck private
or public vehicle parking or storage structures. To
be considered as an open deck vehicle parking or storage
structure 51% or more of all outside walls must be open
between floor and ceiling. If the roof of an open deck
parking, storage or housing structure is used for parking,
it shall be considered a story. [Added 5-11-1989 by
Ord. No. 1657]
VEHICLE SERVICES -- Any area of land, including any
structures there on or any building or part thereof
that is used for the retail sale of gasoline, diesel
or other fuel, kerosene oil or accessories for motor
vehicles and which may include facilities used for polishing,
greasing, washing, dry cleaning or servicing such vehicles;
self service or full server filling stations; any structure
or part thereof used for the repair, spraying and/or
painting of vehicle bodies, chassis, wheels, fenders,
bumpers and/or accessories of automobiles construction,
commercial or pleasure vehicles. [Added 5-11-1989 by
Ord. No. 1657]
B. Words used in the present time include the future
tense. [Added 5-11-1989 by Ord. No. 1657]
C. The term "shall" is always mandatory.
The term "person" includes an individual,
a corporation, a partnership, an incorporated association
or any other similar entity. The term "used"
or "occupied" as applied to any land or structure
shall be construed to include the words "intended,
arranged or designed to be used or occupied." [Added
5-11-1989 by Ord. No. 1657]
85-3. Enforcement.
A. The Fire Marshal shall enforce the Fire Prevention
Code.
B. A report of the Fire Marshal shall be made annually
and transmitted to the Secretary of the township. It
shall contain all proceedings under this code, with
such statistics as the Fire Marshal may wish to include
therein. The Fire Marshal may also recommend any amendments
to the code which in the Fire Marshal's judgment shall
be desirable.
85-4. Amendments to code.
The Fire Prevention Code is amended and changed in
the following respects:
A. F-500.1 shall read as follows:
F-500.1. Permit Required. A permit shall be obtained
from the Fire Official for bowling lane resurfacing
operations involving the use and application of flammable
liquids and materials.
B. F-521.0 shall read as follows:
F-521.0. Lane Resurfacing Operations. Resurfacing operations
shall not be carried on while the establishment is open
for business. The Bureau of Fire Prevention shall be
notified 48 hours in advance when alleys are to be resurfaced.
Proper ventilation shall be provided. Heating, ventilating
or cooling systems employing recirculation of air shall
not be operated during resurfacing operations or within
one hour following the application of flammable finishes.
All electric motors or other equipment in the area which
might be a source of ignition shall be shut down and
all smoking and use of open flames prohibited during
the application of flammable finishes and for one hour
thereafter.
C. F-1000.1 shall read as follows:
F-1000.1. Permit Required. No person shall engage in
the business of dry cleaning without a permit, which
shall prescribe the class of system to be used. The
use of a Class I or Class II system shall be prohibited.
D. There shall be added to Article 12, following F-1210.0,
the following:
F-1210.1. The Fire Official shall have the power to
restrict and regulate the parking of motor vehicles
on all parking lots adjacent to commercial buildings
or buildings open to the public, for the purpose of
providing proper egress by occupants in case of fire
and access of fire equipment.
E. F-1303.2 shall read as follows:
F-1303.2. The storage of explosives and blasting agents
is prohibited except for temporary storage for use in
connection with approved blasting operations; provided,
however, that this prohibition shall not apply to wholesale
and retail stocks of small arms ammunition, explosive
bolts, explosive rivets or cartridges for explosive-actuated
power tools in quantities involving less than 500 pounds
of explosive material.
F. [Amended 6-11-1991 by Ord. No. 1695] Fireworks.
F-2700 shall read as follows:
F-2700.1. Prohibited Activities. The manufacture, storage,
offering for sale, selling at retail, using or exploding
of fireworks is prohibited within the township, except
as provided in Chapter 27 of the BOCA National Fire
Prevention Code/1990, with the further provision that
Section F-2701.3, Exceptions, of said BOCA Code, which
permits wholesale, dealer and jobber sales of fireworks
is deleted in its entirety.
F-2701.1.1. General Requirements for Outdoor Public
Display.
(1) The outdoor public display of fireworks shall be
permitted only in compliance with the standards set
forth in the National Fire Protection Association (NFPA)
Standard 1123, as amended, and only upon application
for and obtaining of a permit from the township.
(2) The Code Official shall determine the necessary
services required to be provided by the township, including
but not limited to police, fire, ambulance and public
works, and the cost of such services shall be paid by
the applicant for the permit.
(3) Upon application for a permit, an escrow fee in
an amount determined by the Code Official to be adequate
for the payment of all expenses which may be incurred
by the township in the providing of services shall be
provided. [Amended 10-8-1992 by Ord. No. 1719]
G. [Amended 3-8-1973 by Ord. No. 1346; 3-11-1976 by
Ord. No. 1420; 3-9-1978 by Ord. No. 1461; 5-11-1989
by Ord. No. 1657; 7-9-1992 by Ord. No. 1714] F-1500.12.
Approved automatic sprinkler equipment required throughout
certain buildings.
(1) General requirements.
(a) Approved automatic sprinkler equipment shall be
installed and maintained throughout buildings and structures
as the type set forth below as hereafter erected, substantially
altered or where the use changes to a more intensive
and/or a more hazardous use as determined by the township.
[1] Commercial.
[2] Educational.
[3] Industrial.
[4] Institutional.
[5] Office.
[6] Public assembly.
[7] Residential.
[8] Vehicle services.
[9] Vehicle parking and storage.
(b) Exceptions.
[1] Automatic sprinklers shall not be required to be
installed in structures or buildings of an educational
type in accordance with the following:
[a] The structure shall have a fire separation distance
of no less than 30 feet from any other structure or
lot line. The structure shall be limited in area within
surrounding exterior walls to 950 square feet.
Exception: Individual classrooms limited to 950 square
feet, with a fire separation wall having a minimum fire
resistance rating of two hours, as defined in the Building
Code. The total area limit of structures so erected
shall be 3,800 square feet.
[b] Each room shall have a minimum of two means of
egress placed a distance apart equal to not less than
1/2 of the length of the overall diagonal dimension
of the area.
[c] Each room shall have a maximum occupant load of
one occupancy per each 30 square feet net in space.
The occupant load shall be so posted near both doors
in a conspicuous location. Occupancy is restricted to
persons seven years of age or older.
[d] The structure shall be equipped with a fire alarm
system connected to central station service as approved
by the Code Official.
[e] The structure shall not be used for any laboratories,
workshops, cooking, the storage or use of any flammable
or combustible liquids, general storage or similar occupancies.
[f] The structure shall have a Class I interior wall
and ceiling finish as defined in the Building Code.
(2) Another approved type of fire protection may be
submitted in a safety deposit or other vault, provided
that it meets the approval of an approved rating bureau
and the Fire Marshal.
(3) Sprinkler protection shall be prohibited in any
location, room, building or structure where the discharge
of water will increase the hazard to life and property.
Such location, room, building or structure which is
used for the manufacturing, mixing, processing or storage
of highly flammable, explosive or toxic ducts, powders,
chemicals or solids shall be protected by another approved
type of protection as acceptable by an approved rating
bureau and the Fire Marshal.
H. (Reserved)EN
I. [Amended 3-8-1973 by Ord. No. 1346; 5-11-1989 by
Ord. No. 1657] F-1500.14 shall read as follows:
F-1500.14 Approved Sprinkler Plans.
(1) Prior to the installation, revision, addition or
alteration of any sprinkler system and/or other fire
protection equipment in any building or structure, detailed
plans shall be first submitted to an approved rating
bureau or agency for approval. Copies of the approved
plans must be submitted and approved by the Fire Marshal.
No occupancy shall be established until the installation,
revision, addition or alteration is complete and approved
by the Fire Marshal.
(2) The automatic sprinkler system shall be connected
to a water supply with sufficient capacity and pressure
to sustain the sprinklers and Fire Department as determined
by an approved rating bureau or agency. Irrespective
of the flow determined, the minimum capacity of not
less than 750 gallons of water per minute with a minimum
residual pressure of 15 pounds per square inch at the
top or end line of sprinklers shall be provided. Any
sprinkler system pipe schedule or hydraulic calculation
density change, if necessary, shall be completed prior
to the establishment of a new occupancy within the sprinklered
building or structure.
(3) (Reserved)EN
(4) Supervised alarm system. In all buildings or structures
where approved central station supervised fire, heat
and/or smoke detector alarm systems are installed such
systems shall comply with the latest National Fire Protection
Association (NFPA) pamphlets Nos. 71, 72-B, 72-D and
74, and any amendments thereto. A permit must be obtained
prior to the installation of any supervised fire, heat
and/or smoke detector alarm system. Upon completion,
the supervised fire, heat and/or smoke detector alarm
system must be inspected for compliance by the Fire
Marshal or his (her) representative.
J. [Amended 3-8-1973 by Ord. No. 1346; 10-12-1978 by
Ord. No. 1474] F-1500.15 shall read as follows:
F-1500.15. Smoke Detectors.
(1) A basic approved, listed and labeled smoke detector
shall be installed to protect each separate sleeping
area and at the head stairway leading to an occupied
area in all residential (single-family, duplex and townhouse)
dwelling units. Each detection device shall cause the
operation of an alarm which will be clearly audible
in all bedrooms over the background noise levels with
all intervening doors closed. The tests of audibility
level shall be conducted with all household equipment,
which may be in operation at night, in full operation.
All alarm-sounding devices shall have a minimum rating
of 85 dBA at 10 feet.
(2) Approved, listed and labeled smoke detectors shall
be installed throughout all hallways, corridors, basements,
subbasements, crawl spaces, trash rooms, storage rooms,
locker rooms, stairwells and recreation rooms in all
institutional, educational, custodial and medical occupancies
and apartments, including, inter alia, apartments, schools,
colleges, dormitories, libraries, gymnasiums, nursing
and convalescent homes, homes for the aged, including
apartments for the aged, rooms and boardinghouses for
the aged, hospitals and therapeutic and prophylactic
sanatoriums, and children's nurseries, including day-care
nurseries, and medical and health centers. All smoke
detectors shall be interlocked so that the alarm will
be transmitted throughout the entire premises.
(3) A basic approved, listed and labeled smoke detector
shall be installed to protect each separate sleeping
area in all apartments, dormitories, nursing and convalescent
homes, homes for the aged, including apartments for
the aged, rooms and boardinghouses for the aged and
therapeutic and prophylactic sanatoriums, medical and
health centers or any other facility, not including
hospitals, where sleeping facilities are provided. Each
detection device shall cause the operation of an alarm
which will be clearly audible in all bedrooms over the
with all intervening doors closed. The tests of audibility
level shall be conducted with all household equipment
which may be in operation at night in full operation.
All alarm-sounding devices shall have a minimum rating
of 85 dBA at 10 feet.
(4) Approved, listed and labeled smoke detectors shall
be installed and maintained throughout the entire premises
in all places of public assembly, including, inter alia,
restaurants, bowling lanes and associated occupancies
within the same structure, shopping malls, shopping
centers, including merchandising marts, indoor places
of amusement, including sports arenas or rinks, clubs,
lodges or fraternal organizations, YMCA or similar occupancies,
lumber yards and builder's supply and all other office,
commercial or industrial properties having a ground
floor area in excess of 2,900 square feet.
(5) General requirements.
(a) All smoke detectors, except detectors in single-family
or duplex dwellings or townhouses, shall be installed
in a standard manner with a two-source power supply.
Both supplies must be sufficient to operate the alarm(s)
for at least four continuous minutes each.
(b) Smoke detectors shall be capable of detecting gray
smoke having a minimum smoke obscuration of 4% per foot
(optical density of 0.0177 per foot).
(c) On smoke detectors requiring a light source for
operation, failure of the light source shall result
in an audible trouble signal. The failure of the light
source shall not cause an alarm signal. The audible
trouble signal shall be produced at least once every
one minute for seven consecutive days.
(d) For each smoke detector requiring a light source,
at least one spare light source bulb shall be provided
with the detector and mounted conveniently in or on
the unit or associated control unit.
(e) All electrical installations must conform to the
National Electrical Code, NFPA Pamphlet No. 70 and all
local ordinances.
(f) The location and spacing of all smoke detectors
shall conform to NFPA Pamphlet Nos. 72A, 74 and 74E.
(g) All smoke detector installations in single-family,
duplex or townhouses shall comply with at least level
four of NFPA Pamphlet No. 74.
(h) All detectors shall be tested semiannually in accordance
with the manufacturer's instructions, and a permanent
record showing all details of the test results shall
be kept on the premises for at least five years. Cleaning
and maintenance of the detectors shall be performed
per the manufacturer's instructions.
(i) The following smoke detectors shall be replaced
or tested by a recognized laboratory:
[1] Detectors on systems restored after disuse.
[2] Detectors that are perceptibly corroded.
[3] Detectors that were painted in the field or cleaned
of paint.
[4] Detectors that were subject to mechanical injury
or similar abuse.
[5] Detectors on circuits that have been subjected
to surges by over-voltage or lightning damage.
[6] Detectors subjected to other conditions, such as
grease or other deposits or corrosive atmospheres.
(j) Location of Smoke Detectors.
[1] Smoke detectors shall be so located and adjusted
to operate reliably in case of smoke at any part of
the area protected. The location of detectors shall
be based upon an engineering survey of the application
of this form of protection to the area under consideration.
These features include air velocity, number of detectors
to provide adequate coverage of cross-sectional areas
of the space with respect to travel, diffusion or stratification
of smoke; location of detectors with respect to exhaust,
intake or circulating blowers; air-conditioning facilities,
temperature variations and the like. Such conditions
vary with different installations and should be dealt
with on the experience in the service.
[2] Special consideration shall be given to the storage
of the contents of a protected space to provide unobstructed
openings for the travel of smoke to the smoke detector.
[3] Where air-conditioning or ventilating equipment
serves the space to be protected by a smoke detector,
particular attention shall be given to the intake, exhaust
and circulation of smoke under any condition of operation
of the equipment to ensure prompt detection.
[4] Photoelectric light beams shall be so located or
enclosed or otherwise arranged that movement of objects
within the space will cause no signal.
[5] Light-sensitive equipment shall be so located or
shielded that light from any other source other than
that intended to be applied to the equipment will have
no effect upon the detector. The opening of any enclosure
during normal servicing shall cause no smoke alarm signal.
A smoke detector shall be so installed as to minimize
the possibility of operation due to accumulation of
dust, moisture, deterioration of equipment or any other
condition of system operation not associated with fire
or smoke.
[6] The conditions of occupancy of each space protected
by a smoke detector shall be arranged to avoid operation
of the detector due to the use of fumigants or any other
type of fog or mist-producing materials, sweeping and
cleaning resulting in dust circulation and the like.
[7] The smoke detection combination shall be able to
withstand 110% of the rated voltage continuously without
injury during the normal supervisory condition and shall
operate successfully during the normal signaling condition
at the increased voltage and also at 85% of normal voltage.
[8] All smoke detecting equipment shall be secured
reliably in place. The security of separate photoelectric
light source and receiver units shall ensure against
the change of adjustment due to vibration, change in
alignment of supporting surfaces or the like.
[9] Provision shall be made to afford adequate protection
of smoke detection equipment from mechanical injury.
(k) Approved Plans.
[1] Prior to the installation, revision, addition to
or alteration of a supervised and approved central station
fire protection device, such system must conform to
the latest edition of the following National Fire Protection
Association pamphlets: No. 71 (Central Station Signaling
Systems), No. 72B (Auxiliary Signaling Systems), No.
72D (Proprietary Signaling Systems), No. 72E (Automatic
Fire Detectors) and No. 74 (Household Warning Equipment)
and any amendments thereto.
[2] When the cost of installation exceeds $100, a permit
must be obtained prior to the installation of any fire,
heat and/or smoke detector alarms in all occupancies.
All fire detection devices shall be approved for the
purpose for which they were intended and shall be installed
per specifications.
[3] Upon completion of the installation, a satisfactory
test of the detector(s) shall be made in the presence
of the Fire Marshal or his representative, and the installing
contractor shall furnish a written statement to the
effect that the detectors have been installed in accordance
with the manufacturer's specifications.
(l) (Reserved)EN
(m) Nothing in this subsection is intended to prevent
the use of new methods or device(s), provided that sufficient
data is submitted to the Fire Marshal or his representative
to demonstrate that the new method or device is equivalent
in quality, effectiveness, durability and safety to
that prescribed by this subsection.
(n) At the enactment of this subsection, all new construction,
structures substantially altered, any structures that
suffered a loss of life due to fire, any structure that
suffered a property loss in excess of $1,000 from fire
or any change of ownership or occupancy in any structure
shall comply with this subsection immediately. All other
structures and occupancies shall comply with this subsection
within two years of the enactment of this subsection.
K. [Amended 6-13-1974 by Ord. No. 1377] F-1500.16 shall
read as follows:
F-1500.16 Special provisions for all high-rise multiple-occupancy,
office, dwelling, institutional, educational or storage
buildings with an elevation of more than six stories
or 65 feet in height above the mean grade level: These
buildings shall conform to the requirements of this
section in addition to all other requirements of the
codes of the Township of Abington. Requirements are
listed as follows:
(1) Elevators. The use of capacitance or photoelectric
operation of elevator doors shall be prohibited.
(a) Provide products-of-combustion detectors in all
elevator shafts.
(b) Provide emergency power and lighting in all elevators.
(c) Provide voice communication with fire command station,
which shall be interlocked with detectors in all elevators.
(d) Provide emergency control which will return all
elevators to the fire command floor upon activation
of any products-of-combustion or other fire alarm. During
emergencies, all elevators shall be under the control
of the fire command station.
(e) All elevators shall be enclosed within smokeproof
towers of at least a two-hour fire-resistance rating.
Elevators may not be located within the same enclosures
as stairs.
(2) Stairs.
(a) All stairs shall be enclosed in shafts or towers
of at least a two-hour fire-resistance rating.
(b) Emergency telephones shall be installed on not
less than every fourth floor in each stair enclosure.
(c) All stair enclosures shall be provided with an
approved intercommunication system interlocked with
the fire command station.
(d) All stair enclosures shall be smoke-proof or provided
with any other means that will prevent smoke from entering
the stair enclosure.
(e) All stair enclosures shall be provided with fire
doors approved for Class B openings. Doors shall be
provided with products-of-combustion closures as a means
of positive closing and shall be interlocked with the
fire command station during emergencies. All interior
stair doors shall remain unlocked except on the street
floor or where a fail-safe electric door lock is activated
by the detector.
(3) Manual Fire Alarm Box. A manual fire alarm box
shall be located adjacent to exits into stairway enclosures
and in every elevator lobby. This alarm box shall be
interlocked with the fire command station and also with
the voice communication system. The system shall be
designed in accordance with the latest issue of the
National Fire Protection Association standards according
to Pamphlets Nos. 71, 72A and 72B.
NOTE: In cases where the elevator shaft and stairs
are adjacent to each other, only one fire alarm box
is sufficient.
(4) Voice Communication System.
(a) There shall be two separate approved continuously
electrically supervised voice communication systems;
one system shall be used as a Fire Department communication
system and one system shall be used as a public voice
communication system between the fire command station
and the following areas:
[1] Elevators, elevator lobbies, corridors and stairways.
[2] All areas in excess of 1,000 square feet.
[3] Each dwelling unit and hotel guest room.
[4] Warden's station on each floor.
[5] Mechanical control center.
(b) When approved, the Fire Department system may be
combined with the public voice communication system.
(c) Both the detection system and the alarm system
shall activate a voice alarm system capable of being
operated from the fire command station on both the general
and the selective basis and dependent upon the compartmentation
involved. The alarm shall be designed to be heard by
all occupants within the building or the designated
portions thereof, as specified for the public voice
communication system. The elevator lobby shall also
be connected to this system.
(5) Fire Command Station. A cutoff fire-resistive fire
command station used strictly for Fire Department operations
shall be provided in a location approved by the district
fire company and the Fire Marshal. The fire command
station shall be provided with the following:
(a) All voice communication panels.
(b) Fire alarm and detection panels.
(c) Public and inter-building telephones.
(d) Standby power controls.
(e) Sprinkler valve tamper and water flow detectors.
(f) Direct transmission to central station or Fire
Department.
(g) Status indicators and controls for elevators and
air-handling systems.
(h) Means to control all sounding devices throughout
the building.
(i) All panels shall have visual display lamps or systems
and a means of testing same.
(j) Individual manual operation of each air supply
and each exhaust system unless provided in the mechanical
control center and in the room containing the affected
fans.
(6) Firesafety Directors. There shall be at least one
Firesafety Director in each building, who shall supervise
at least one qualified Fire Warden on each floor. Mandatory
fire drills shall be held monthly on various floors
of the building. At least two meetings, with records,
shall be conducted each month between the Firesafety
Director and the Fire Wardens.
(7) Standpipes and Hand Hose. All structures in excess
of six stories or 65 feet in height above mean grade
and not more than 250 feet in height shall be equipped
with not less than six-inch standpipes. Requirements
for standpipes shall be as follows:
(a) Standpipes shall be located with outlets within
hose cabinets.
(b) Standpipes shall be protected from freezing and
mechanical and fire damage.
(c) Standpipes shall be installed progressively with
the erection of the building.
(d) When more than one standpipe is required in a structure,
they shall be interconnected at their bases and every
10 stories by pipes of a size equal to that of the largest
riser.
(e) Each standpipe riser shall be equipped with O.S.
& Y. valves so as to permit each section to be taken
out of service if damaged or broken without interrupting
the water supply to other sections or risers.
(f) Standpipes shall be equipped with a two-and-one-half-inch
hose connection and a one-and-one-half-inch hose connection
with valves and threads conforming to the Township of
Abington's standard, located not more than five feet
above the floor.
(g) Standpipes located inside structures shall have
not less than 100 feet of one-and-one-half-inch diameter
hose and approved spray nozzle and couplings conforming
to the requirements of the Township of Abington's standards
at each outlet and suspended in an approved rack or
cabinet. All hose shall be capable of withstanding at
least 100% in excess of the pressure on the risers with
fire pumps in service.
(h) Each standpipe shall be equipped with an approved
siamese Fire Department connection constructed of approved
corrosion-resistive metal, located in an area as prescribed
by the district fire company and the Fire Marshal and
not less than 18 inches nor more than three feet above
grade.
(i) All standpipe installations and piping not covered
in this section shall conform to the latest edition
of Pamphlet No. 14 according to the National Fire Protection
Association and ordinances of the Township of Abington.
(8) Public Water Supply. There shall be a looped water
main around the building to supply the required water
hydrants and required supply within the building. Mains
shall be of the required size but in no case less than
six inches. Location of hydrants shall conform to the
designation of the district fire company and the Fire
Marshal. At least one hydrant shall be located within
100 feet of the Fire Department connection for the sprinklers
and standpipe supply. All threads for the fire protection
shall be National Standard type.
(9) Sprinkler Protection. Sprinkler protection shall
be provided throughout the entire building and the sprinkler
system shall be equipped with the following:
(a) Complete central station supervisory service, including
valve tamper, water flow, low air, pump operation or
any other protection required.
(b) Shutoff valves and water flow devices shall be
provided on each floor.
(c) The sprinkler system shall be looped between the
standpipe risers at the bottom, top and mid-height in
all buildings with a maximum of 10 stories served by
any loop. Check valves shall be installed at each loop
level.
(d) A minimum of two approved fire pumps independently
driven shall be provided and sized for the sprinkler
demand and for a minimum of 500 gallons per minute for
Fire Department standpipe operations.
(e) There shall be a two-source water supply for the
sprinkler system and standpipe system in the building.
The primary supply must be capable of supplying at least
1,000 gallons per minute with a twenty-pound residual
pressure. The secondary supply must be equal to a one-hour
demand or 30,000 gallons on a combination sprinkler
system and standpipe operation, whichever is greater.
The secondary supply shall be available automatically
if the primary supply falls.
(f) A sprinkler system that is hydraulically designed
using the parameters as set forth by Chapter 8 of National
Fire Protection Association Pamphlet No. 13 may be provided
as an alternative to the standard sprinkler installation
pending the approval of an approved rating bureau, district
fire company and the Fire Marshal only in a building
that is occupied solely for office occupancy.
(10) Compartmentation. Compartmentation shall be provided
throughout every building to assure areas of refuge
for the building occupants. Areas shall be provided
as follows:
(a) No compartment shall exceed 10,000 square feet.
(b) Compartmented areas shall be provided with approved
detectors.
(c) Compartment separations shall be of at least a
two-hour fire-resistance rating.
(d) Horizontal exits into each compartment shall be
of the approved type with approved doors suitable for
Class B openings.
(e) All stairwells from compartments shall be provided
with smokeproof enclosures or any other means that will
prevent the passage of smoke from one compartment to
another.
(f) When openings in exterior walls are located vertically
above one another, compartmentation is also required
between stories by either horizontal or vertical flame
barriers at the exterior walls. All flame barriers shall
extend at least 30 inches beyond the exterior wall in
the plane of the floor.
(11) Detectors. An approved system which will provide
for automatic detection of the products of combustion
other than heat shall be installed in the following
locations:
(a) All hallways and corridors.
(b) All high-hazard occupancy areas.
(c) All mechanical equipment rooms.
(d) All lobbies, stair and elevator enclosures.
(e) All rooms in excess of 5,000 square feet.
(f) All areas used for the manufacture, sale, process
or storage of combustible products.
(g) All return-air portions of each air-conditioning
and mechanical ventilation system that serves floors
other than the floor on which the equipment is located.
Sensitivity of the detectors shall be set to operate
within the proper limitations so that the greatest sensitivity
is achieved without transmission of false alarms.
(12) Smoke Control. Mechanical ventilation for the
removal of the products of combustion shall be provided
in each story and shall consist of the following:
(a) An approved shaft through which smoke and heat
can be mechanically vented to the outdoors. The size
of the shaft shall be uniform throughout and of such
dimensions as to provide 60 air changes per hour in
the largest compartment anywhere in the building. Openings
into the shaft shall be protected with an automatic
single-piece shutter located as high as possible in
the room and designed to vent the entire compartment.
Under fire conditions, the return and exhaust air shall
be moved directly to the outside without any recirculation
to other sections of the building. Actuation shall be
by the detection system or the sprinkler system.
(b) Approved panels or windows installed in the exterior
walls shall be opened from an approved location other
than the fire floor. Such venting facilities shall be
provided at the rate of 20 square feet per 50 lineal
feet of exterior wall in each story, whichever is greater,
and distributed around the perimeter at not more than
fifty-foot intervals. Such panels shall be identified
clearly as required by the Fire Department. The use
of tempered glass in lieu of openable panels is prohibited.
(c) Any other approved design which will produce equivalent
results.
(13) Standby Power Generator. A permanently installed
standby power generator system conforming to Pamphlet
No. 70 of the National Fire Protection Association shall
be provided. The system shall be equipped with a suitable
means for automatically starting the generator set upon
failure of the normal electrical service and for the
automatic transfer and operation of all required electrical
functions at full power within 60 seconds of such normal-service
failure. System supervision, with manual start and transfer
features, shall be provided at the fire command station.
An on-premises fuel supply sufficient for not less than
two hours' full-demand operation of the system shall
be provided. All power, lighting, signal and communication
facilities provided under the requirements of this section
shall be transferable to the standby power system. The
power requirements shall be determined so as to provide
service to, but not limited to, the following:
(a) Entire fire protection and alarm system equipment.
(b) Exit lights and all other emergency lighting.
(c) Required mechanical ventilation.
(d) All elevators designated for fire protection use.
(e) Entire voice communication system.
(f) All equipment within the fire command station.
L. There shall be added to Article 17, Section F-1700.0,
the following:
(a) Location with respect to property lines. The minimum
distance of any part of an aboveground tank for the
storage of flammable liquids other than crude petroleum
to the nearest line of adjoining property which may
be built upon shall be not less than the distance indicated
in the following table:
Capacity of Class of Minimum
Tank Flammable Distance
(gallons) Liquid (feet)
0 to 275 III 5
276 to 550 III 10
M. [Amended 12-13-1973 by Ord. No. 1366] F-1700.1 shall
read as follows:
F-1700.1. The storage, handling and processing of liquids
with a flash point below 200 F., and of liquids with
a flash point above 200 F. which, when heated, will
assume the characteristics of liquids with flash points
below 200 F., except as provided in Section F-110.2.
(a) The storage, handling or use of Class I or Class
II flammable liquids in a dwelling or other place of
human habitation shall be prohibited.
(b) The storage, handling or use of Class I or Class
II flammable liquids in any other building or occupancy
shall be limited to five gallons. This amount must be
stored in and dispensed from approved safety cans suitable
for that purpose.
(c) The storage, handling or use of Class I or Class
II flammable liquids in aboveground tanks inside or
outside of buildings is prohibited. The storage, handling
or use of Class III flammable liquids in aboveground
tanks with a capacity of more than 550 gallons outside
or inside of buildings shall be prohibited.
(d) No Class I, Class II or Class III flammable liquid
bulk plant shall be constructed within the limits of
the Township of Abington.
The storage or use of flammable liquids in the fuel
tank of a motor vehicle, aircraft, motorboat, mobile
power plant or mobile heating plant shall be permitted.
The storage or use of paints, oils, varnishes or similar
mixtures when such liquids are stored for maintenance,
painting or similar purposes for a period of not more
than 30 days shall be permitted.
The sale, storage and use of Class I or Class II flammable
liquids in portable containers exceeding five gallons
capacity shall be prohibited and only approved containers
shall be used for this amount.
The sale of Class I or Class II flammable liquids in
portable containers to any person, firm or corporation
shall be limited to one five-gallon approved container.
N. There shall be added to Article 22, Section F-2200.0,
the following:
Bulk storage of liquefied petroleum gas shall be provided
except in PI-zoned districts.
O. [Amended 9-13-1973 by Ord. No. 1361] F-2200.1 shall
read as follows:
F-2200.1 Permits and Reports of Installation. A permit
shall be obtained from the Fire Official for each installation
of liquefied petroleum gas employing a container or
an aggregate of interconnected containers of over 125
gallons water capacity, and for each permanent installation,
irrespective of size of containers, made at buildings
in which people congregate for civic, political, educational,
religious, social or recreational purposes. Such buildings
shall include schools, churches, hospitals, institutions,
hotels and restaurants, each having a capacity of 20
or more persons. Prior to making such installation,
an installer shall submit plans to the Fire Official,
and if compliance with the requirements of this code
is shown by said plans, a permit shall be issued.
P. [Amended 9-13-1973 by Ord. No. 1361] F-2200.11 shall
read as follows:
F-2200.11. Records. The Fire Official shall maintain
a record of all liquefied petroleum gas installations
employing a container or an aggregate of interconnected
containers of over 125 gallons water capacity (not including
installation of gas-burning appliances and replacing
of portable cylinders).
Q. [Amended 9-13-1973 by Ord. No. 1361] F-2210.3 shall
read as follows:
F-2210.3. Location of Containers. Distribution plants
whose primary purpose is the distribution of liquefied
petroleum gas are prohibited in all zones. An installation
of liquefied petroleum gas employing a container or
an aggregate of containers in excess of 1,200 gallons
water capacity shall be prohibited, except that in particular
installations this capacity limit may be altered at
the discretion of the Fire Official after consideration
of special features such as topographical conditions,
nature of occupancy and proximity to buildings, capacity
of proposed tanks, degree of private protection to be
provided and facilities of the local Fire Department.
R. [Amended 9-13-1973 by Ord. No. 1361] F-2210.4 shall
read as follows:
F-2210.4. Pressures Inside of Buildings. Gas for fuel
purposes in either the liquid or vapor phase shall not
be piped into any building at pressure in excess of
20 pounds per square inch gauge except as follows:
(1) Buildings or portions of buildings separated from
other portions by walls, partitions and floor and ceiling
assemblies of noncombustible material having a fire-resistance
rating of not less than two hours, used exclusively
to house internal-combustion engines or industrial processes.
(2) Buildings or portions of buildings separated from
other portions by walls, partitions and floor and ceiling
assemblies of noncombustible material having a fire-resistance
rating of not less than two hours, used exclusively
for research and experimental laboratories.
(3) Buildings, structures or equipment under construction
or repair. Portable containers shall not be taken into
buildings except as provided in Section F-2210.5.EN
S.EN[Amended 9-13-1973 by Ord. No. 1361] F-2210.5 shall
read as follows:
F-2210.5 Containers Inside Buildings. Containers and
first-stage regulating equipment shall be located outside
of buildings other than buildings provided for this
purpose, except containers and regulating equipment
may be used indoors under the following conditions:
(1) If temporarily used for demonstration purposes
and the container has a maximum water capacity of 12
pounds.
(2) If used with a completely self-contained gas hand
torch or similar equipment and the container has a maximum
water capacity of 21/2 pounds.
(3) In use as a motor fuel.
All liquefied petroleum gas tanks in excess of 125
gallons water capacity shall be provided with an enclosure
consisting of at least a six-foot-high industrial-type
fence. Each tank shall be provided with suitable devices
which can be locked in place and prevent the unauthorized
operation of any container appurtenances, system valves
or equipment.
All permitted liquefied petroleum gas installations
shall be regulated by National Fire Protection Association
Pamphlet No. 58, 1972 Edition, and any future amendments
thereto.
T. There shall be added to Article 26, Section F-2630.0,
the following: "All pot-type and gravity-feed heating
and cooking appliances are prohibited in the Township
of Abington."
U. F-2918.0 shall read as follows:
F-2918.0: In all buildings where automatic fire extinguishing
systems are required in kitchens or areas where food
is prepared by cooking, a metal grease hood with metal
filters and metal ductwork leading to the outside and
above the roof line shall be installed according to
National Fire Protection Association Regulation No.
96. Such hood and filters shall be kept clean at all
times. In such installations, automatic shutoff valves
shall be installed on gas-heating appliances used for
cooking, and automatic cutoff switches shall be installed
on electrical appliances used for cooking. Such valves
and switches shall shut off the heat source when the
fire extinguishing system is activated.
V. Permit and inspection fees shall be designated by
resolution of the Board of Commissioners of the Township
of Abington, which fees shall be established from time
to time. A permit shall not be issued until the designated
fees have been paid. Failure to pay designated fees
shall be considered a violation of this code. [Added
10-8-1992 by Ord. No. 1719]
W. [Added 4-14-1994 by Ord. No. 1741] F-319.0 shall
read as follows:
SECTION F-319.0 KEY BOXES
F-319.1 Installations. When access to a property or
structure or access to an area within that property
or structure is unduly difficult because of secured
openings and where immediate access may be necessary
for lifesaving and/or fire-fighting purposes, the property
owner or occupant may obtain a permit to install a key
box or boxes as approved by the Fire Marshal.
F-319.2 Application. This section shall apply to the
following properties or structures:
(1) All new and existing office, storage, institutional,
commercial and manufacturing buildings.
(2) All new and existing residential buildings.
(3) Any other structure or premises.
F-319.3 Promulgation of Rules and Regulations; Compliance.
All key boxes installed pursuant to this section shall
be of a type approved by the Fire Board. The Fire Board
may promulgate reasonable rules and regulations to implement
this section relating to key boxes. Violations of the
rules and regulations shall be considered a violation
of this code.
F-319.4 Contents of Key Boxes. Key boxes should contain:
(1) Keys and/or magnet cards to locked points of ingress,
whether on the interior or exterior of such property.
(2) Keys and/or magnet cards to locked mechanical equipment
rooms.
(3) Keys and/or magnet cards to locked electrical rooms
or panels.
(4) Keys and/or magnet cards to locked elevator rooms
or controls.
(5) Keys and/or magnet cards to other areas as directed
by the Fire Marshal.
(6) Hazardous materials information, as defined in
Section F-2902.0.
F-319.5 Custody of Keys.
(1) Keys to key boxes shall be held only by the Fire
Marshal and authorized personnel of the Fire Department.
(2) Keys issued to the Fire Department for key boxes
will be kept on the apparatus or in the possession of
authorized Fire Department personnel.
(3) The Fire Marshal shall retain custody of a key
for the purpose of emergencies or placing new or replacement
items in the key boxes.
85-5. Modifications and deletions. [Amended 10-11-1990
by Ord. No. 1684; 5-13-1993 by Ord. No. 1729]
A. Modification. The Board of Commissioners shall have
power to modify any of the provisions of the Fire Prevention
Code upon application, in writing, by the owner or lessee
or the duly authorized agent of either, when there are
practical difficulties in the way of carrying out the
strict letter of the code, provided that the spirit
of the code shall be observed, public safety secured
and substantial justice done. The particulars of such
modification when granted or allowed and the decision
of the Board of Commissioners thereon shall be entered
upon the records of the Board of Commissioners, and
a signed copy shall be furnished the applicant.
85-6. Appeals. [Amended 5-13-1993 by Ord. No. 1729]
Whenever the Fire Marshal shall disapprove an application
or refuse to grant a permit applied for or when it is
claimed that the provisions of the code do not apply
or that the true intent and meaning of the code have
been misconstrued or wrongly interpreted, the applicant
may appeal from the decision of the Fire Marshal to
the Township Manager within 30 days from the date of
the decision appealed.
85-7. New materials, processes or occupancies. [Amended
5-13-1993 by Ord. No. 1729]
The Township Manager shall determine and specify, after
giving affected persons an opportunity to be heard,
any new materials, processes or occupancies which shall
require permits, in addition to those now enumerated
in said code. The Fire Marshal shall post such list
in a conspicuous place in the Fire Marshal's office
and distribute copies thereof to interested persons.
85-8. Violations and penalties. [Amended 5-13-1993
by Ord. No. 1729]
A. Any persons who shall violate any of the provisions
of the code hereby adopted or fail to comply therewith
or who shall violate or fail to comply with any order
made thereunder or who shall build in violation of any
detailed statement of specifications or plans submitted
and approved thereunder or any certificate or permit
issued thereunder and from which no appeal has been
taken or who shall fail to comply with such an order
as affirmed or modified by the Board of Commissioners
or by a court of competent jurisdiction, within the
time fixed therein, shall, severally, for each and every
such violation and noncompliance, be liable, on conviction
thereof, to a fine of not more than $300 and, in default
of payment thereof, to imprisonment for not more than
five days. The imposition of one penalty for any violation
shall not excuse the violation or permit it to continue,
and all such persons shall be required to correct or
remedy such violations or defects within a reasonable
time; and, when not otherwise specified, each day that
prohibited conditions are maintained shall constitute
a separate offense.
B. The application of the above penalty shall not be
held to prevent the enforced removal of prohibited conditions.
Top
|